Burnham Series 8H/8HE Boiler Foglio Delle Specifiche

Pagina di 4
 
 
SERIES 8H ATMOSPHERIC: 
      GAS FIRED HOT WATER BOILER 
               SUGGESTED SPECIFICATIONS
 
 
 
Note:   To use as a project specification: 
              A.  Insert, in the blank spaces provided, the applicable model number, capacity, fuel, and electrical data. 
           B.  Delete the item in parentheses or marked “*” which are not applicable to the project requirements. 
 
      C.  Insert, where applicable, optional non-standard features desired.
 
1.   GENERAL SPECIFICATION 
Contractor shall furnish and install, where indicated on the drawings,  ______ (quantity) Model  8_____H  gas fired 
hot water boiler(s) having an I=B=R approved gross output of  _______ MBH and a net rating of  _______ MBH per 
boiler with an input of _______ MBH when fired with  (natural or LP gas).   Boiler(s) shall be constructed of cast iron 
sections manufactured in accordance   with ASME requirements for low pressure boilers and each section shall be 
permanently marked with the ASME symbol and the maximum allowable working pressure.
 
2.  BOILER EQUIPMENT SPECIFICATION 
 
*2.1      The boiler(s) shall be knocked down with the sections and base factory assembled as one  unit.  The knocked 
                     down boiler shall be shipped in a fully containerized shipping crate, capable of being stacked two high. 
 
*2.2      The boiler(s) shall be factory packaged with jacket, manifold, burner, and controls mounted and wired.  The  
                      packaged boiler shall be shipped on a wooden skid with reinforced cardboard to protect from damage. 
 
  2.3      Boiler sections shall have pin-like projections on each center section, evenly spaced on the vertical flue        
 
           surfaces to extract the maximum heat from the hot flue gases. 
 
  2.4      Boiler sections shall be surface ground to ensure smooth positive mating surfaces. 
 
  2.5      Boiler sections shall be assembled with precision machined cast iron push nipples, pressed into a mating     
 
           machined nipple port in the section eliminating the need for any  gasket material which would be subject to  
 
           deterioration due to corrosion or oil based chemicals. 
 
  2.6      All boiler sections shall be individually hydrostatically tested for 50 psi water working pressure in             
 
           accordance with ASME Code Section IV. 
 
  2.7      Boiler shall have top access individual cleanout openings between sections. 
 
  2.8      Boilers shall be equipped with aluminized steel burners with air shutters which feature smooth ignition and  
 
           positive flame extinction. 
 
  2.9      Boiler flue canopy shall be constructed of heavy gauge aluminized steel and shall be concealed under an     
 
           insulated steel boiler jacket. 
 
  2.10     A drafthood shall be furnished for each boiler. 
 
*2.11     Boiler shall be equipped with an automatic flue vent damper.  (standard on size 805H) 
 
  2.12     The boiler jacket shall be deluxe extended type with 3” insulation and have a rust resistant baked enamel     
 
           finish.  The jacket shall be capable of being installed after system piping has been connected to the boiler    
 
           section assembly.  
 
  2.13    Boiler trim shall include a 3-1/2” round pressure-temperature gauge with separated scales for pressure and   
 
           water temperature.  In addition, an ASME approved water relief valve shall  be furnished sized to exceed the 
 
           boiler gross output capacity and shall be factory set to  relieve pressure at (30) (50) psi.