York UL R134A Manuale Utente

Pagina di 140
JOHNSON CONTROLS
4
Specifications
POWER AND ELECTRICAL 
•   Johnson  Controls  has  over  25  years  of  experience 
designing variable speed drives specifically for chiller 
applications.  The result is an extremely reliable air 
cooled chiller system that offers industry leading ef-
ficiency at real world operating conditions, valve-less 
compressor  loading/unloading,  excellent  capacity 
control, high power factor and soft start.
•   All controls and motor starting equipment necessary 
for unit operation shall be factory wired and function 
tested.
•   VSD  Power/Control  Panel  includes  main  power 
connection(s),  VSD  and  fan  motor  contactors,  cur-
rent overloads, and factory wiring.  Standard design 
includes NEMA 3R (IP55) rating, powder painted steel 
cabinet with hinged, latched, and gasket sealed outer 
doors equipped with wind struts for safer servicing.
•   VSD  section  of  power  panel  includes  a  dedicated 
inverter for each compressor. 
•   The  panel  includes  control  display  access  door  so 
display and control features can be accessed without 
opening main cabinet doors.
•   Two and three compressor models come standard with 
single point power connection. In addition, all models 
are supplied with a factory mounted and wired control 
transformer that will supply all unit control voltage from 
the main unit power supply.  The transformer utilizes 
scheduled line voltage on the primary side and pro-
vides 115V/1Ø on secondary.
•   The standard power panel is equipped with terminal 
block electrical connections at the point of incoming 
power. An optional factory mounted circuit breaker is 
available, at point of incoming single point connection, 
that provides the means to disconnect power and short 
circuit  protection.   The  optional  lockable  operating 
handle extends through the power panel door so that 
power may be disconnected without opening any panel 
doors.
•   Short Circuit Withstand Rating of the chiller electri-
cal enclosure is 30,000 Amps for standard terminal 
block connection.  Ratings IAW (in accordance with) 
UL508. (See Accessories and Options section: Can 
be increased to 65,000 Amps for 380, 400 & 460V).  
•   Compressor motors are powered by a variable speed 
drive.   Therefore,  motor  current  never  exceeds  the 
rated load amps (RLA), providing soft starts with no 
electrical inrush.  This eliminates the motor heating 
and  stress  always  found  with  conventional  motor 
starters.  In addition, by eliminating the heat build up 
during starting, the required off-time between starts is 
reduced to a maximum of two minutes.
•   Many  utility  companies  charge  an  additional  fee 
if  power  factor  is  below  0.95.   These  power  factor 
adjustments/penalties  can  affect  both  regular  tariff 
rates, as well as demand charges.  All YCIV models 
have a full load power factor of 95% and maintain this 
level throughout the operating range.  Specifications 
should always require the installing contractor to be 
responsible for additional cost to furnish and install 
power factor correction capacitors if they are not fac-
tory mounted and wired.
S E M I - H E R M E T I C   Y O R K   T W I N   S C R E W 
COMPRESSORS
Johnson  Controls  Engineered  Systems’  Chiller  Design 
Team has developed a world class compressor with un-
equaled performance:
•   Continuous function, microprocessor controlled, VSD 
provides valveless, smooth capacity control from 100% 
down to 10% of chiller capacity for two compressor 
chillers and 100% down to 7.5% for three compressor 
chillers.  In addition, elimination of the slide valve and 
associated unloading components resulted in a 50% 
reduction in compressor moving parts.  
•   Compressors  are  direct  drive,  semihermetic,  rotary 
twin-screw type, including: muffler, temperature ac-
tuated  ‘off-cycle’  heater,  rain-tight  (IP55)  terminal 
box, discharge shut-off service valve, and precision 
machined  cast  iron  housing  mounted  on  neoprene 
isolators.
•   Reliable suction gas cooled, high efficiency, acces-
sible hermetic compressor motor, full suction gas flow 
through 0.006” maximum mesh screen, with inherent 
internal thermal overload protection and external cur-
rent overload on all three phases.
•   Suction gas screen and serviceable, 0.5 micron full 
flow oil filter within the compressor housing.
•   Cast  iron  compressor  housing  precisely  machined 
for optimal clearances and superb efficiency. Entire 
compressor, from suction to discharge has a Design 
Working Pressure of 350 PSIG (24 bar) or higher.
REFRIGERANT CIRCUIT
•   Independent refrigerant circuits per compressor, each 
using  copper  refrigerant  pipe  formed  on  computer 
controlled  bending  machines. This  eliminates  over 
60% of system piping brazed joints as compared to 
designs that use fittings, resulting in a highly reliable 
and leak resistant system.
•   Liquid  line  components  include:  liquid  line  shut-off 
valve with charging port, low side pressure relief de-
vice, high adsorption removable core filter-drier, sight 
glass with moisture-indicator, and electronic expansion 
valve.