Digital Dosing Units 
33
Alarms
 
Several alarm options are available for the Digital Dosing feeder.  The standard unit comes with 
a flashing alarm symbol 
 on the faceplate.  Options include both audible horns and flashing 
lights.  An optional no voltage alarm relay can be connected to the user’s central alarm system.   
Level Probes 
To adjust the level probes: 
 
1.  Turn the controller ON. 
 
2.  Fill the dosing station until the level sensor is one-third covered. 
 
3.  Remove the small plastic screw (M3) on the back of the level sensor (see Figure 
7). 
 
LED Yellow (Station)
        on: Station Filled
        off: Station Emptied
LED Green (Level Probe)
        on: Power Supply Available
        off: Power Supply Not Available
Trim-pot with
Plastic Screw M3
Cable
Blind Lid
Protective Screw
npn: Normally Closed
pnp: Normally Open
1
0
npn: Normally Open
pnp: Normally Closed
Level Probe
 
Figure 7.  Level Sensor Screw 
 
4.   Turn the trim-pot until the yellow control lamp just switches off. 
 
NOTE:   Turning the trim-pot to the left decreases the switching sensitivity; turning it to the 
right increases the switching sensitivity. 
 
5.  Fill the dosing station until the level probe is two-thirds covered.  The yellow 
control lamp should now switch on again.  If not, repeat Step 4. 
 
6.  Reinstall the plastic screw (M3). 
 
NOTE:  The sliding switch under the cover must be set on “0”.