Operator system
Introduction
5/3
Siemens ST PCS 7 · November 2007
5
■
Technical specifications
1)
If every OS client has access to all OS servers/pairs of servers
Definitions
Process object
(PO)
A process object (PO) is a synonym for an opera-
ble and observable block with approx. 30 to 50
individual OS variables (parameters). Thus the
quantity framework data of the engineering sys-
tem can be compared with those of the operating
system.
OS variable
An OS variable or parameter is a defined memory
location required for operating and monitoring
with the operator system; values can be written
into it and read from it (e.g. setpoint, actual value
etc.). A PO usually has several OS variables
(which can be operated and monitored).
Licensing
As of SIMATIC PCS 7 V7.0, the OS software will
only be licensed on the basis of POs. This signifi-
cantly simplifies calculation of the required
license. An average of 50 OS variables will be
calculated for a PO, where motors, valves etc.
require fewer variables, and controls, dosing
functions etc. require more variables. Checking of
the license will also be carried out using the POs,
and additionally includes checking of the total
number of OS variables used.
Every block fulfilling the following criteria is
Every block fulfilling the following criteria is
counted and calculated as a PO:
• It is not a driver block.
• It can be operated and monitored.
• It can send messages.
• It is not a driver block.
• It can be operated and monitored.
• It can send messages.
Process objects
OS variables (approx.)
250
12500
1000
50000
2000
100000
3000
150000
5000
250000
8500
425000
OS quantity framework
Max. number of OS servers / pairs
of servers
12
Max. number of automation systems
per OS server / pair of servers
64
Max. number of OS clients in multi-
client mode
1)
(per multi-user system)
32
Max. number of monitors per
operator station with multi-channel
operation
4
Max. number of OS areas
64
Max. number of windows per
monitor
1 to 16 (adjustable)
Number of trends per trend window 10
Selection time for OS area display
Selection time for OS area display
(100 process symbols)
< 2 s
Max. number of process objects:
• Per OS single station
• Per OS single station
5000 POs
• Per OS server
8500 POs
Max. number of configurable mes-
sages per server/single station
150.000
Number of process tags
• Per OS single station
• Per OS single station
Approx. 3000
• Per OS server
Approx. 5000
• Per multi-user system
Approx. 60000
Integral high-performance archive
system
system
(cyclic buffer), based on Microsoft
SQL server, for:
• Process value archiving (per
• Process value archiving (per
OS server / single station)
Approx. 1000/s
• Message archiving
(per OS server / single station)
Steady-state load approx. 10/s
Message peak approx. 3000 / 4 s
Message peak approx. 3000 / 4 s
Long-term archiving
• Process value archiving with
StoragePlus
Process values from up to 4 sin-
gle stations, servers or pairs of
servers
- Process values of one server
Approx. 1000/s
- Process values of all servers
Approx. 1600/s
• Process value archiving with
central archive server (CAS)
Process values from up to 11
servers or pairs of servers
- Process values of one server
Approx. 1000/s
- Process values of all servers
Approx. 10000/s