Operator system
Introduction
5/3
Siemens ST PCS 7 · November 2007
5
Technical specifications
1)
If every OS client has access to all OS servers/pairs of servers
Definitions
Process object 
(PO)
A process object (PO) is a synonym for an opera-
ble and observable block with approx. 30 to 50 
individual OS variables (parameters). Thus the 
quantity framework data of the engineering sys-
tem can be compared with those of the operating 
system.
OS variable
An OS variable or parameter is a defined memory 
location required for operating and monitoring 
with the operator system; values can be written 
into it and read from it (e.g. setpoint, actual value 
etc.). A PO usually has several OS variables 
(which can be operated and monitored).
Licensing
As of SIMATIC PCS 7 V7.0, the OS software will 
only be licensed on the basis of POs. This signifi-
cantly simplifies calculation of the required 
license. An average of 50 OS variables will be 
calculated for a PO, where motors, valves etc. 
require fewer variables, and controls, dosing 
functions etc. require more variables. Checking of 
the license will also be carried out using the POs, 
and additionally includes checking of the total 
number of OS variables used. 
Every block fulfilling the following criteria is 
counted and calculated as a PO:
• It is not a driver block.
• It can be operated and monitored.
• It can send messages.
Process objects
OS variables (approx.)
250
12500
1000
50000
2000
100000
3000
150000
5000
250000
8500
425000
OS quantity framework
Max. number of OS servers / pairs 
of servers
12
Max. number of automation systems 
per OS server / pair of servers
64
Max. number of OS clients in multi-
client mode 
1)
(per multi-user system)
32
Max. number of monitors per 
operator station with multi-channel 
operation
4
Max. number of OS areas
64
Max. number of windows per 
monitor
1 to 16 (adjustable)
Number of trends per trend window 10
Selection time for OS area display 
(100 process symbols)
< 2 s
Max. number of process objects:
• Per OS single station
5000 POs
• Per OS server
8500 POs
Max. number of configurable mes-
sages per server/single station
150.000
Number of process tags
• Per OS single station
Approx. 3000
• Per OS server
Approx. 5000
• Per multi-user system
Approx. 60000
Integral high-performance archive 
system
(cyclic buffer), based on Microsoft 
SQL server, for:
• Process value archiving (per 
OS server / single station)
Approx. 1000/s
• Message archiving 
(per OS server / single station)
Steady-state load approx. 10/s 
Message peak approx. 3000 / 4 s
Long-term archiving
• Process value archiving with 
StoragePlus
Process values from up to 4 sin-
gle stations, servers or pairs of 
servers
- Process values of one server
Approx. 1000/s
- Process values of all servers
Approx. 1600/s
• Process value archiving with 
central archive server (CAS)
Process values from up to 11 
servers or pairs of servers
- Process values of one server
Approx. 1000/s
- Process values of all servers
Approx. 10000/s