Siemens TV Converter Box G120 Manuale Utente

Pagina di 147
 
 
 
 
 
 
 
    
Automation and Drives - SCE 
 
 
 
 
T I A  Training Document
 
Page 71 of 147 
 Module  
 
     H01 
Issued: 02/2008 
  Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET 
Preface         Notes         Startup with PROFIBUS         Startup with PROFINET         Program Example 
 
36. Ultimately, the ’master control’ has to be ’returned’. It should be ensured that no other ON 
command is pending. (
→ Steuerhoheit abgegeben → Ja) 
 
 
Setpoint and commands from set sources
Please make sure that no ON command from the CPU (automation) is pending. 
Although the PC removes all enables before returning the master control, the setpoints and commands subsequently come 
again from the parameterized sources. If a setpoint is pending there, the drive responds immediately! This can be dangerous. 
Do you want to continue? Yes  No 
 
37. Now you can control the SINAMICS G120 as desired with the Basic Operator Panel (BOP). 
 
 
 
The buttons are assigned as follows: 
 Start motor 
 Stop motor 
 Reversal 
 Take motor to the inching mode 
 Increase speed 
 Decrease speed