TC12 Installation, Commissioning & Maintenance Handbook 
Table 8 - Integral OTU Line Level Switch (S3) 
 
← 
  Switch 
Number 
 
 
→ 
Output 
Power
 
SW 1 
SW 2 
SW 3 
SW 4 
SW 5 
SW 6 
0 dBm 
0  
-3 dBm 
1  
-6 dBm 
0  
-9 dBm 
1  
-10 dBm 
0  
-13 
dBm 0 0 0 0 
 
-16 
dBm 0 0 0 1 
 
Receive 
Threshold
 
 
 
 
-42 dBm 
 
-39 dBm 
 
-33 dBm 
 
 
          0 
Switch 
Open 
 
 
 
 
 
 
 
 
 
 
1 = Switch Closed 
 
Warning -   For use in the UK the power level must not be set to greater 
than  
-13 dBm. Only settings in the non-shaded area are allowed. 
 
6.3.3  Connectors and Cables 
6.3.3.1  Extended System Bus Ribbon Cable 
Connect the Controller extended system bus cable to Plug PLA on the back of the 
Integral OTU PCB. 
 
Note:  Do not connect/disconnect the cable whilst the controller power is 
switched on. 
 
Table 9 - Integral OTU PLA - 40 Way Connector 
PIN
 
NAME
 
 
 
1  
 
ADDRESS BIT 0 
 
ADDRESS BIT 1 
 
ADDRESS BIT 2 
 
ADDRESS BIT 3 
 
ADDRESS BIT 4 
666/HE/43100/000  
Page 170 