Schneider Electric ALTIVAR 58 TRX Manuale Utente
Altivar
®
58 TRX AC Drives
Wiring Recommendations
©
2000–2003 Schneider Electric All Rights Reserved
102
09/2003
Ratings for Input Line Currents, Type H Variable Torque 208/230 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 4 kHz, ATV58HD28M2 to D46M2 at 2 kHz
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 4 kHz, ATV58HD28M2 to D46M2 at 2 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
5000 AIC
10000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
kW
HP
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU29M2•
1.5
2
7.5
9.4
8.6
—
—
—
—
6.6
5.9
ATV58HU41M2•
2.2
3
10.6
13
11.8
—
—
—
—
9.5
8.5
ATV58HU54M2•
3
4
14.3
17.2
15
—
—
—
—
12.6
11.2
ATV58HU72M2•
4
5
16.7
21.4
19.5
—
—
—
—
16.9
14.6
ATV58HU90M2•
5.5
7.5
24.2
29
26.4
32.1
28.4
34.7
30
23.3
20.6
ATV58HD12M2•
7.5
10
30.8
38.3
35
42.3
37.4
44.4
38.2
32.3
28.6
ATV58HD16M2•
11
15
46.2
41.7
37.8
41.7
38
41.7
38
41.7
38
ATV58HD16M2•
15
20
60
55.5
50.5
55.7
50.5
55.7
50.8
55.1
50.5
ATV58HD23M2•
18.5
25
75
67
61.8
67.2
61.8
67.2
61.8
67.1
61.4
ATV58HD28M2•
22
30
88
80.5
73.3
80.6
73.3
80.9
73.6
80.7
73.6
ATV58HD33M2•
30
40
116
107.6
97.9
108.4
97.9
108.4
98.5
107.6
98.5
ATV58HD46M2•
37
50
143
134.8
121.2
135.4
121.2
135.5
124
135
123.7
Ratings for Input Line Currents, Type H Variable Torque Low Noise 208/230 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 8 kHz, ATV58HD28M2 to D46M2 at 4 kHz
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 8 kHz, ATV58HD28M2 to D46M2 at 4 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
5000 AIC
10000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
kW
HP
A
208V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU29M2•
1.5
2
7.5
9.4
8.6
—
—
—
—
6.6
5.9
ATV58HU41M2•
2.2
3
10.6
13
11.8
—
—
—
—
9.5
8.5
ATV58HU54M2•
3
4
14.3
17.2
15
—
—
—
—
12.6
11.2
ATV58HU72M2•
4
5
16.7
21.4
19.5
—
—
—
—
16.9
14.6
ATV58HU90M2•
5.5
7.5
24.2
29
26.4
32.1
28.4
34.7
30
23.3
20.7
ATV58HD12M2•
7.5
10
30.8
38.3
35
35.7
32.4
35.8
32.8
35.2
32.8
ATV58HD16M2•
11
15
46.2
42.7
39
42.7
39
42.7
39
42.4
39
ATV58HD23M2•
15
20
60
55.2
48.9
55.2
50.5
55.4
51.2
55.4
50.7
ATV58HD28M2•
18.5
25
75
67.8
61.9
68.2
62.1
68.4
62.6
67.6
61.6
ATV58HD33M2•
22
30
88
82
73.8
82
75.1
82.8
76.7
82.8
76.5
ATV58HD46M2•
30
40
116
108.6
97.3
109.2
99.2
109.7
99.7
109.4
99.7
NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.