Powermaster Safety Gate UL 991 Manuale Utente

Pagina di 22
 
27 
MASTER/SLAVE INSTALLATION 
 
NOTE:  A single unit is considered a Master. In a 
Master/Slave installation, one unit must be converted to 
LEFT HAND operation. 
 
ON
SLAVE
JUMPER
ON
SLAVE
JUMPER
MASTER
POSITION
(OFF)
SLAVE
POSITION
(ON)
 
 
1. Place jumper on the MASTER  operator’s control 
board in the “OFF” position. 
 
2.  Place jumper on the SLAVE operator’s control board 
in the “ON” position. 
 
3.  Connect terminal #15 of MASTER unit to terminal #5 
of slave unit. 
 
4.  Connect terminal #16 from the Master unit to terminal 
#6 on the Slave unit. 
 
5.  Connect terminal #17 from the Master unit to terminal 
#7 on the Slave unit. 
 
 
28 
MASTER
SLAVE
1     2      3     4      5     6      7      8     9    10    11    12    13   14                      15    16   17    18
1     2      3     4      5     6      7      8     9    10    11    12    13   14                       15    16   17    18
 
 
TIMER TO CLOSE OPTION 
 
The operator is equipped with a timer to close option for use 
with control devices such as a radio control, or card key 
control.  The AUTO RECLOSE TIMER adjustment screw is 
located on the printed circuit board. The operator is shipped 
from the factory with this timer preset to the off position; fully 
counter clockwise.  As the timer adjustment screw is rotated 
clockwise, the closing of the gate can be delayed from 2 
seconds to 60 seconds.   
 
AUTO
CLOSE
TIMER
60 SEC
2 SEC
OFF
LOCATION OF
AUTO CLOSE TIMER
ADJUSTMENT
Figure 12