Toshiba 18 - 1250 A Manuale Utente

Pagina di 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
31 
5.5.3 
Jog Mode Functions 
 
 
 
 
 
 
 
 
5.5.4 
Kick Start Mode Functions 
 
 
 
 
 
 
 
 
5.5.5   Decel Mode Functions 
 
 
 
 
 
 
 
 
 
 
 
 
 
5.5.6   Restart Function 
 
 
 
 
 
 
 
Fn #  Group 
Function Description 
Adjustment / Display Range 
Setting 
Increments 
Factory 
Setting 
Section
F019 
Jog M
odes
 
Voltage Jog 
5 – 100% Line Voltage 
1% 
50% 
5.6.3 
and 
4.2.5.b 
F020 
Time of Voltage Jog 
1 – 20 Seconds 
1 second 
10 
seconds 
F021 
Current Jog 
100 – 500% Motor
 
Current 1% 
150% 
Table 5.5.3: Jog Mode Function Group 
Fn #  Group 
Function Description 
Adjustment / Display Range 
Setting 
Increments 
Factory 
Setting 
Section
F022 
Kick Mo
de
 
Kick Start Voltage 
0 = Disabled, or  
10 - 100% Line Voltage 
1% 
Disabled 
5.6.4 
F023 
Kick Start Time 
0.1 - 2 Seconds 
0.1second 
0.8 
seconds 
Table 5.5.4: Kick Start Mode Function Group 
Fn #  Group 
Function Description 
Adjustment / Display Range 
Setting 
Increments 
Factory 
Setting 
Section
F024 
Pump Flex Dec
e
Mode
 
Pump Flex Control  / 
Deceleration Ramp  
0 = Disabled (coast to stop)  
1 = Enabled, except after OL trip 
2 = Enabled, continued Decel even 
if there is an OL trip 
Disabled 
5.6.5 
and 
Append. 
F025 
Begin Decel Level (BDL), 
Immediate Drop Down Torque 
0 - 100 % of Output Voltage 
1% 
60% 
F026 
Decel Shut Off Voltage 
0 to (BDL minus 1)% Voltage 
1% 
30% 
F027 
Decel Ramp Time 
1 – 60 Seconds 
1 second 
10 
seconds 
Table 5.5.5: Pump Flex Decel Mode Function Group 
Fn #  Group 
Function Description 
Adjustment / Display Range 
Setting 
Increments 
Factory 
Setting 
Section
F028 
Restart
 
Restart Delay Time  
(Sequential Start Delay) 
0 = Disabled, or 
1-999 seconds after a Power Loss 
(Status can be read in F054) 
1 second 
Disabled 
5.6.6 
F029 
Reserved for Factory Use 
 
 
 
 
Table 5.5.6: Restart Function Group