10. Heater
Location
Use the clearances in Paragraph 8; the combustion air requirements in Paragraph 9;
the mounting height requirements, throw information, sound data, and location rec-
ommendations below; the weights in Paragraph 11; and the venting requirements in
Paragraph 24 to determine where to suspend the heater.
Mounting Height
Locate the heater so that it is a minimum of 15 feet (4.6M) above the floor and in
compliance with the clearances in Paragraph 8.
WARNING: If touched, the vent pipe and internal heater surfaces
that are accessible from outside the heater will cause burns. Suspend
the heater a minimum of 15 feet (4.6M) above the floor.
CAUTION: Do not locate the heater where it may be exposed to
water spray, rain, or dripping water.
Heater Throw -
All Models
NOTES:
X = Distance from “0” to beginning
of floor coverage.
Y = Distance from “0” to end of
floor coverage.
Length of floor coverage = Y - X.
Z = Distance from “0” to the point
where the air velocity drops below
50 feet (15.2M) per minute.
Throws listed are with standard
louvers facing one direction and
fully open. Throw pattern changes
with louver angle, 2-way louver
direction, and or optional 4-way
louvers.
Throw (feet and meters)
FIGURE 3 - Model LDAP Air Throw (Heat Mode @ High Speed) - Applies to All Sizes
= “Rear” of Heater Discharge
Mounting
Height
Standard Louvers
30° Nozzle
60° Nozzle
X
Y
Z
X
Y
Z
X
Y
Z
Standard
Louvers
30° Nozzle
60° Nozzle
0
X
Y
Z
X
Y
Z
X
Y
Z
20
5
55
134
40
90
146
70
125
158
30
8
53
121
44
86
133
76
119
145
40
12
49
109
47
81
120
N/A
N/A
N/A
50
17
45
96
N/A
N/A
N/A
N/A
N/A
N/A
X
Y
Z
X
Y
Z
X
Y
Z
6.1
1.5
16.8
40.8
12.2
27.4
44.5
21.3
38.1
48.2
9.1
2.4
16.2
36.9
13.4
26.2
40.5
23.2
36.3
44.2
12.2
3.7
14.9
33.2
14.3
24.7
36.6
N/A
N/A
N/A
15.2
5.2
13.7
29.3
N/A
N/A
N/A
N/A
N/A
N/A
M
o
unti
n
g
 
Hei
g
ht 
(Meters
)
Standard Louvers
30° Degree Nozzle
60° Degree Nozzle
Throw (meters)
M
o
unti
n
g
 
Hei
g
ht 
(feet)
Standard Louvers
30° Degree Nozzle
60° Degree Nozzle
Throw (feet)