Omron Healthcare VARISPEEDF7 Manuale Utente

Pagina di 25
EN-10
Fig 6  Flywheel Diode Connection
Digital o
u
tput signals
M1
During run (NO)
Closed during Run
Function 
selected by H2-
01 to H2-03
Relay contacts
Contact capacity: 
1 A max. at 250 VAC 
1 A max. at 30 VDC
*3
M2
M3
Zero speed (NO)
Closed when output 
frequency at zero level 
(b2-01) or below 
M4
M5
Speed agreement detection 
(NO)
Within ± 2 Hz of set fre-
quency when ON
M6
MA
Fault output signal
Closed across MA and MC during faults
Open across MB and MC during faults
MB
MC
Ana
log ou
tput signals
FM
Output frequency 
Analog output fre-
quency signal;
0 to 10 V; 10V=FMAX 
Function 
selected by 
H4-01
0 to +10 V max. ±5%
2 mA max.
-10 to +10 V max. ±5%
2 mA max
4 to 20 mA
AC
Analog common
AM
Inverter output power
Analog output power 
signal;
0 to 10V; 10V=max. 
appl. motor capacity
Function 
selected by 
H4-04
Pulse I/O
RP
Pulse Input
H6-01 (Frequency reference input) 
*4
0 to 32 kHz (3k
Ω
High level voltage 3.5 to 
13.2 V
MP
Pulse Output
H6-06 (Output frequency)
0 to 32 kHz
+15 V output (2.2k
Ω
)
RS-485/42
2
R+
MEMOBUS communications 
input
For 2-wire RS-485, short R+ and S+ 
as well as R- and S-.
Differential input, 
PHC isolation
R-
S+
MEMOBUS communications 
output
Differential input, 
PHC isolation
S-
IG
Signal common
*1. The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-
step speed setting 
          1 for S6 and multi-step speed setting 2 for S7.
*2. Do not use this power supply for supplying any external equipment.
*3. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in 
*4. Pulse input specifications are given in the following table:
Low level voltage
0.0 to 0.8 V
High level voltage
3.5 to 13.2 V
H duty
30% to 70%
Pulse frequency
0 to 32 kHz
IMPORTANT
1. In 
 the wiring of the digital inputs S1 to S7 is shown for the connection of contacts or NPN transis-
tors (0V common and sinking mode). This is the default setting. 
For the connection of PNP transistors or for using a 24V external power supply, refer to 
.
2. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when con-
necting a DC reactor. 
Type
No.
Signal Name
Function
Signal Level
External power: 
30 VDC max.
Coil
Flywheel diode
1 A max.
The rating of the flywheel diode must 
be at least as high as the circuit volt-
age.