219
Analog Input Functions
Section 7-9
Auxiliary Area
Word
Bits
Function
Settings
Controlled 
by
A550
00 to 15
Analog Input PV
Contains the value input from the analog input port 
(using either the END refresh or immediate refresh) 
in 4-digit hexadecimal.
The PV range depends on the input range:
• 0 to 10 V:
FE70 to 20D0 hex
• 0 to 5 V or 1 to 5 V: FF38 to 1068 hex
−10 to 10 V:
DDA0 to 2260 hex
Motion 
Control 
Module
A552
00
Analog Input 
Status
Analog Input
User Adjustment 
Completed
OFF: Not adjusted
ON:
Adjustment completed
01 to 06
Reserved
07
Analog Sampling 
Started
OFF: Not started
ON:
Started
08
Factory Adjustment 
Data Error
OFF: No Error
ON:
Error 
(Checked at startup.)
09
User Adjustment 
Data Error
OFF: No Error
ON:
Error 
(Checked at startup.)
10 to 14
Reserved
---
15
Analog Input 
Status
Analog Input
Analog Sampling 
Overlap
OFF: Normal sampling
ON:
The next sampling 
operation occurred 
before the present 
sampling operation 
completed.
Motion 
Control 
Module
A559
01 to 15
Analog Input 
Status
Analog Input
Number of Samples Indicates the number of data 
samples actually input since 
sampling started.
Motion 
Control 
Module
A560
00 to 15
Analog Out-
put 1 Output 
Value
When an END refresh is selected, the 4-digit hexadecimal value set 
here by the user is output from analog output port 1.
When immediate refreshing is selected, the 4-digit hexadecimal value 
being output from analog output port 1 is stored here for monitoring. 
The output value range depends on the output range, as shown below.
• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex
−10 to 10 V: EA84 to 157C hex
Note
1. Set the analog output method (END or immediate refreshing) with the 
System Setup’s output method setting. A setting of 0 hex specifies an 
END refresh. This setting applies to both analog output 1 and 2.
2. Specify the output range with the output 1 setting.
With imme-
diate 
refresh: 
Motion 
Control 
Module
With END 
refresh: 
User
A561
00 to 15
Analog Out-
put 2 Output 
Value
This word has the same settings as the analog output 1 output value 
(A560), above. (When an END refresh is selected, set the value to out-
put from analog output port 2. When an immediate refresh is selected, 
the output value is stored here for monitoring.)
Note
1. Set the analog output method (END or immediate refresh) with the 
System Setup’s output method setting. A setting of 0 hex specifies an 
END refresh. This setting applies to both analog output 1 and 2.
2. Specify the output range with the output 2 setting.