Chapter 1  Uninterruptable Power Supply (UPS) Overview    17
UPS Installation and Configuration Guide
UPS threshold values
UPS threshold values are tolerances that define the UPS operational requirements and power 
delivery capability. The UPS reports the threshold values through the Unified Manager. The 
following table provides the minimum and maximum UPS threshold values for 110~120 and 
220~240 Volt standards. All configuration data is stored in the F:\Program 
Files\PwerChute\PwrChute.ini file.
Alarm and event reporting
The BCM software monitors the UPS threshold values and provides event reporting capability to 
the BCM simple network management protocol (SNMP) trap and alarm reporting systems. The 
BCM monitors the UPS through the COM port and polls the UPS every 60 seconds. Power supply 
failure notification is sent to the OAM and alarm subsystem and to the recovery application. 
The threshold values relate to the following:
Power: Utility power failure, low battery power for the UPS device. The message advises 
users to take appropriate action on their BCM. The battery must be recharged for every minute 
of run time. Appropriate action is to verify the power supply is functional. Alternatively, try to 
connect to a secondary power supply, possibly switch telephony/data services to alternate 
location if possible.
Communications: Send a message when communication with the UPS starts. Send a message 
when communication with the UPS is lost (such as remote UPS shutdown). If communication 
loss occurs, verify that serial connection is functional or UPS is operational.
110 ~ 120 Volt UPS Threshold Values
220 ~ 240 Volt UPS Threshold Values
Minimum
Maximum
Minimum
Maximum
Line voltage minimum (AC)
1
90
120
208
253
Line voltage maximum (AC)
2
90
120
208
253
UPS output voltage (AC)
3
106
127
220
240
Battery voltage (DC)
4
16
36
16
36
Output frequency (Hz)
5
59
60.25
49
50.25
UPS load (%)
6
0
125
0
125
Temperature (degr. C)
7
-15
45
-15
45
1 Line voltage minimum: The lowest AC input voltage supplied by the power source. This threshold represents the 
value recorded since you started the user interface module.
2. Line voltage maximum: The highest AC input voltage supplied by the power source. This threshold represents the 
value recorded since you started the user interface module.
3. UPS Output voltage: The voltage (AC) supplied by the UPS to the equipment supported. 
4. Battery voltage: The voltage (DC) supplied by the UPS to the equipment supported during a power outage.
5. Output frequency: The line voltage frequency.
6. UPS load: The amount of battery power drawn by the equipment supported during a recorded interval. The value 
is represented by the percentage of the total power available in the UPS. 
7. Temperature: The internal temperature of the UPS device.