Kidde Fire Systems Surge Protector P/N 81-CO2MAN-001 Manuale Utente

Pagina di 324
Component Descriptions
P/N 81-CO2MAN-001
2-71
September 2013
2-8.7
Odorizer Assembly
The odorizer assembly injects a scent of wintergreen into the carbon dioxide during a 
discharge. Upon discharge, the carbon dioxide pressure ruptures a burst disc to release the 
scent of wintergreen. This scent warns personnel in the vicinity of the area protected by the 
fire suppression system that carbon dioxide gas is present. An odorizer assembly is required 
with each CO
2
 system regardless of size. 
Figure 2-77.  Odorizer Assembly
8.7” REF