Kidde Fire Systems Surge Protector P/N 81-CO2MAN-001 Manuale Utente

Pagina di 324
Table 3-2A. Volume Factors - Surface Fires (For 34% CO
2
 Concentration), US Units
Enclosure Volume (ft.
3
)
Volume Factor
Calculated Quantity
 
f
1
 
f
2
 
(ft.
3
/lb.)
(lb./ft.
3
)
Not Less Than (lb.)
Up to 140
14
0.072
--
141 - 500
15
0.067
10
501 - 1,600
16
0.063
35
1,601 - 4,500
18
0.056
100
4,501 - 50,000
20
0.050
250
Over 50,000
22
0.046
2,500
Ducts and Covered Trenches 
(See Section 3-5.2.2.1)
8
0.125
--
Design
September 2013
3-6
P/N 81-CO2MAN-001
3-5.2.2
BASIC TOTAL FLOODING QUANTITY
The discharge of carbon dioxide into an enclosure will displace a portion of the atmosphere in 
the enclosure. The displaced atmosphere is exhausted freely from the enclosure through 
openings or vents as the carbon dioxide is discharged. Since some suppression agent is lost 
with the vented atmosphere, the volume of carbon dioxide required to develop a given 
concentration will be greater than the volume that actually remains in the enclosure. This 
method of application is called "free efflux" flooding.
A small volume has proportionally more surface (or boundary) area per unit of enclosed volume 
than a larger volume, and has a proportionally greater leakage rate. Accordingly, larger 
quantities of carbon dioxide per unit of enclosed volume are injected into smaller volumes to 
account for the higher leakage rates anticipated upon discharge. The quantity of carbon dioxide 
per  unit  volume  is  called  the  Volume  Factor  and  is  shown  in  Table 3-2.  Also  note  that  the 
minimum quantity of CO
2
 is specified for the smallest volume in each group to avoid a possible 
overlap of CO
2
 requirements.
(Equation 1)
or
Where:
= Basic quantity of agent, lb.(kg)
 = 
Enclosure 
volume, 
ft.
3
 (m
3
)
ft.
3
/lb.(m
3
/kg)
= Volume factor from Table 3-2, lb./
ft.
3
 (kg
3
/m
3
)
W
B
V
f
1
=
W
B
V
f
2
=
W
B
V
f
1
f
2