AUXILIARY EQUIPMENT AND SYSTEMS
A sub-system of components is used to provide auxiliary interlocks that occur at system 
actuation. Such interlocks may include electrical connections, such as fan or process shutdown, 
and/or mechanical operations, such as door or vent closure.
Where the continuing operation of equipment associated with a hazard being protected could 
contribute  to  sustaining  the  fire  in  that  hazard,  the  source  of  power  or  fuel  shall  be 
automatically shut off.
NOTE This does not apply to lubricating oil systems associated with large rotating equipment, 
where an extended discharge system is provided and that is designed to operate for the 
deceleration/cooldown period.
All shutdown devices shall be considered integral parts of the system and shall function with 
the system operation.
3-15.1
Pressure Operated Switches
One or more Pressure Operated Switches (Part No. 81-486536-000 or 81-981332-000) may 
be used for auxiliary electrical functions such as HVAC shut down, closing motorized dampers, 
or providing a release signal to the building alarm system. Refer to Paragraph 2-8.1 for 
additional information.
3-15.2
Pressure Operated Trips
One or more Pressure Operated Trips (Part No. 81-874290-000) may be used for auxiliary 
mechanical functions such as damper closure, door closure, or mechanical gas valve shutdown. 
Typical applications of the pressure-operated trip are shown in Figure 3-13. Reference 
Paragraph 2-8.2 for additional information.