Kidde Fire Systems Surge Protector P/N 81-CO2MAN-001 Manuale Utente

Pagina di 324
Installation
P/N 81-CO2MAN-001
4-37
September 2013
The 1/8-inch copper tubing to the HADs must be protected by 1/2-inch EMT. Water which 
collects in the conduit line and freezes may damage the tubing. This necessitates the draining 
of all low points in tubing conduit which are subject to freezing. If necessary, drill a small hole 
in the conduit or fitting at the low point.
Install the pneumatic detectors on the ceiling of the protected space. Connect each detector 
on a detection system branch line to 1/2-inch conduit. Terminate single branch line conduit at 
a junction box near the pneumatic control head. Conduit bends must be rounded smoothly. 
Fasten and securely brace the conduit. Use standard junction boxes where required to make 
connections.
Run 1/8-inch copper tubing through the conduit, checking each section of tubing for 
obstructions with a manometer prior to installation and prior to making connections, as shown 
in Figure 4-29. Connect the tubing sections by means of flared fittings and connect each 
detector as shown.
Terminate the 1/8-inch tubing for single branch line systems at the junction box near the 
control head. Connect the 1/8-inch tubing to 3/16-inch tubing in the junction box by means of 
a reducing union, and then route 3/16-inch tubing from the junction box to the pneumatic 
control head.
Figure 4-29.  Manometer Pneumatic Detection
CAUTION
Do not damage or drill through tubing.
5
4
3
2
1
2
0
1
2
3
4
5
FILL HERE
MANOMETER TEST SET
P/N WK-840041-000
RUBBER
BULB
C
PNEUMATIC
CONTROL
HEAD
1/8 in. NUT P/N WK-207648-000
1/8 in. TUBING-FLARE END WITH NUT-
CUT OTHER END SQUARE
3/16 in. FEMALE FITTING
3/16 in. X 17 in. (432 mm)
LONG TUBING P/N WK-802366000
3/16 in. - 1/8 in.
UNION
P/N 81-802536-000
(REMOVE 1/8 in.
NUT)
RUBBER
TUBE
B
RUBBER
TUBE
A
1/8 in.
UNION
1/8 in.
NUT
SYSTEM
ACTUATION
TUBING
INDUSTRIAL
DETECTOR P/N
WK-840845-000
1/8 in. UNION
AND NUT
P/N 81-802535-000
FILL
TO
HERE