Kidde Fire Systems Surge Protector P/N 81-CO2MAN-001 Manuale Utente

Pagina di 324
P/N 81-CO2MAN-001
B-9
September 2013
B-7.1
Lockout Valve Installation
The construction of the two-way union end ball valve product design helps make installation 
and maintenance easy. This product has the "free floating" ball principle. The ball is not fixed 
and is free to align under line pressure. The resulting benefit from this feature of the valve 
design is a tight shut-off with the flow in either direction, regardless of the position of the valve 
in the pipeline. In order to facilitate maintenance, the assembly consists of a union on each 
side of the valve body.
The lockout valve with limit switch must be installed in the discharge pipe network, 
downstream of all cylinders, check valves, and directional/stop valves. Lockout valves can be 
installed in either the vertical or horizontal position using good pipe fitting practices. Place two 
to three wraps of Teflon tape on male threads of pipe. Attach lockout valve unions to pipe, but 
do not fully tighten at this time. Rotate the valve body into position, then tighten both unions.
1. Use Teflon tape or paste on male threads.
2. Can be installed vertically and horizontally.
3. Should be locked in the "open" position using a padlock. 
4. Must be located downstream of ALL cylinders and should be easily accessible.
5. Must be electrically supervised.
B-7.1.1
STEM SEAL ADJUSTMENT
If leakage is evident in the stem packing area, tighten the adjusting nut (the nut beneath the 
handle) 1/8 turn. If the leak persists, repeat the above.
Note: The switches and the corresponding cams are preset by the valve assembly supplier to 
the configurations indicated below. No adjustment to the cams is required. When the 
cam is engaged with the switch, the switch contacts are closed, thus closing the 
normally open contacts. Terminals 1 through 6 are used with the microswitches. 
Terminals 7 and 8 are for optional equipment not part of this assembly. 
Switch 1 can also be wired to provide positive (LED, strobe, bell etc.) indication that the 
valve is fully closed.
Switch 2 must always be wired in series with the electric control head in the releasing 
circuit. 
Note: The limit switch assembly consists of two (2) single pole, double throw (SPDT) 
mechanical switches, which are rated to 15 amps.
Table B-2. CO
2
 Lockout Valve with Limit Switch Specifications
General Dimensions
Assembly 
Part Number
Size
A
B
C
D
E
F
G
81-934711-000
1/2 in.
(DN15)
21/32 in.
(17 mm)
3-15/19 in.
(100 mm)
1-15/16 in.
(49 mm)
2-1/4 in.
(57 mm)
5-1/2 in.
(140 mm)
2-51/64 in.
(71 mm)
2-1/2 in.
(64 mm)
81-934712-000
3/4 in.
(DN20)
13/16 in.
(21 mm)
4-1/2 in.
(114 mm)
2-3/16 in.
(56 mm)
2-39/64 in.
(66 mm)
5-1/2 in.
(140 mm)
2-51/64 in.
(71 mm)
2-1/2 in.
(64 mm)
81-934713-000
1 in.
(DN25)
1 in.
(25 mm)
4-15/16 in.
(125 mm)
2-3/8 in.
(60 mm)
2-63/64 in.
(76 mm)
6-1/2 in.
(165 mm)
2-51/64 in.
(71 mm)
2-1/2 in.
(64 mm)
81-934714-000
1-1/2 in.
(DN40)
1-7/16 in.
(37 mm)
5-7/8 in.
(149 mm)
2-3/4 in.
(70 mm)
3-7/8 in.
(98 mm)
8-1/2 in.
(216 mm)
2-51/64 in.
(71 mm)
2-3/4 in.
(70 mm)
81-934715-000
2 in. 
(DN50)
1-23/32 in.
(44 mm)
6-7/8 in.
(175 mm)
3-3/8 in.
(86 mm)
4-1/2 in.
(114 mm)
8-1/2 in.
(216 mm)
2-51/64 in.
(71 mm)
2-3/4 in.
(70 mm)