B-8.4
Semi-annual Maintenance for Odorizer Cartridge
For systems using the odorizer cartridge, Part No. 10030080, disassemble the odorizer and 
verify that the odorizing cartridge is still intact on a semi-annual basis.
B-8.5
Post Discharge Odorizer Maintenance
1. Remove the union nut and cylinder body from the odorizer assembly, leaving just the union 
headpiece attached to the piping. 
2. Use a small pick or slotted screwdriver to remove the spiral retaining ring and the circular 
screen. Remove all glass particles.
3. Carefully insert the odorizing cartridge into the cylinder body. This is most easily done by 
holding the cylinder body on its side. The narrow tip end of the odorizing cartridge should 
go into the cylinder body first. DO NOT drop the odorizing cartridge into the cylinder body, 
as this will most likely break the odorizing cartridge. 
4. Replace the screen and secure with the spiral retaining ring. Make sure the o-ring is still in 
its groove before placing the cylinder body back onto the union head piece. A small amount 
of o-ring lubricant can be used to help keep the o-ring in place. 
5. Thread the union nut back onto the odorizer assembly and tighten the assembly.