Specifications
GF 400 DV Sebago
Specifications
Input Rates
Natural Gas
32,000 BTU/hr. maximum input
 18,000 BTU/hr. minimum input
Propane
 32,000 BTU/hr. maximum input
 16,000 BTU/hr. minimum input
Inlet Pressure:
          MIN
MAX
Natural Gas:
 5.0 WC  (1.24 kPa)        7.0 WC  (1.74 kPa)
Propane:
12.0 WC  (2.99 kPa)    14.9 WC  (3.71 kPa)
Manifold Pressure:
       MIN
MAX
Natural Gas:
1.2 WC (.30 kPa)       3.8 WC  (.95 kPa)
Propane:
2.9 WC (.722 kPa)        11.0 WC  (2.74 kPa)
Piezo Ignitor / Standing Pilot
25 1/2”*
647 mm
28 1/2”*
724 mm
29”
737 mm
26 1/2”
673 mm
13”
330 mm
19 1/2”
495 mm
19 5/8”
500 mm
28 1/2”
724 mm
26 1/2”
673 mm
CL
Suggested Tools for
Installation and Service
• External regulator (for Propane only)
• Piping which complies with local code
• Manual shutoff valve  (T-Handle in Massachusetts)
• Sediment trap - if required by code
• Tee joint
• Pipe wrench
• Pipe sealant
• 10 mm open end wrench
• 1/2”, 7/16” open end wrench or deep socket
• Phillips head screwdriver
• Flat head screwdriver
• 1/4” nut driver
• 4 mm allen wrench
• Gloves
• Safety glasses
• Torx T20 screwdriver
• Leak test solution
• Reciprocating Saw
• Power Drill
*For height with 6” Legs, subtract 2 1/4”