Lifebreath CONTROLAIR 15 200MAX Manuale Utente

Pagina di 32
8
Model MAXTOP
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
- Each air stream has one centrifugal 
blower driven by a common PSC motor. 5 speed fan operation. 
120 VAC, 1.4 Amps.
FILTERS
- Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
- Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied
with the unit.
DEFROST
- Recirculating damper defrost system.
DEHUMIDISTAT
- Adjustable Internal Dehumidistat.
CASE
- Twenty gauge prepainted galvanized steel (G60) for superior 
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections  2 -  1/2" (12 mm) OD.
CONTROLS
- ControlAir 15
WEIGHT
87 lbs. (39.5 kg)
SHIPPING WEIGHT
89 lbs. (40.5 kg)
PERFORMANCE 
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
196 
(93)
@ 0.2” (50 Pa)
188 
(89)
@ 0.3” (75 Pa)
178 
(84)
@ 0.4” (100 Pa)
165 
(78)
@ 0.5” (125 Pa)
149 
(71)
Maximum Temperature Recovery
80%
Sensible Effectiveness 
@ 117 cfm (55 L/s ) 
(CSA C439M)
72%
Sensible Efficiency 
@ 117 cfm (55 L/s)    32
O
F (0°C)
64%
Sensible Efficiency 
@ 67 cfm (31 L/s)    -13
O
F (-25°C)
70%
VAC @ 60HZ
120
WATTS / Low speed
74
WATTS / High speed
164
Amp rating
1.4
TOP VIEW
SIDE VIEW
 25 1/2 "
(648 mm)  
26 1/2"
(673 mm) 
22 1/2" 
(572 mm)
FRONT VIEW
ALL DUCT CONNECTIONS
ARE 6" (150  mm)
 18"
(457 mm)
 7 1/2"
(191 mm) 
SUPPLY OF
FRESH AIR
FRESH AIR 
SUPPLY
TO  BUILDING
STALE AIR
RETURN FROM 
BUILDING
STALE AIR
EXHAUST
DRAIN
CONNECTION
CONTROLS
*Service Clearance
25" (635 mm) 
¤
DIMENSIONS MAXTOP
 
 
inches (mm)
OPTIONS
99-104    
Digital Electronic Timer
- 20/40/60 min. 
99-105    
Programmable Ventilation Control
(PVC)
includes Programmable Time Clock, Dehumidistat 
and Air Sentry™
99-109    
Air Sentry
™ Air Quality Monitor designed to 
accept remotely mounted Control Pad
99-250
Ventilation Dehumidistat - 
Dehumidistat designed
to accept remotely mounted Control Pad
99-163   
Duct Heater
w/ Electronic SCR Thermostat, 1 Kw, 
6” (150mm)
99-164   
Duct Heater
w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)
99-186   
Weatherhoods
, Two - 6” (150mm) 
c/w 1/4” (6mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and 
a 5 year replacement parts warranty.
TI-100-NE
0103
DATE: __________________________
PROJECT: __________________________________________
MECHANICAL CONTRACTOR: _____________________________
511 McCormick Blvd.
London, Ontario  
N5W 4C8
Ph: (519) 457-1904
Fx: (519) 457-1676
Email:  nutech@lifebreath.com