Liebert Universal Monitor Manuale Utente
System and Control Options
60
9.8
Setup System - Setup Modem & Pagers
To use the modem and pager features, be sure to connect the phone line connector to a telephone wall
jack using an RJ11 cord, as described in 4.6.2 - Phone Line Connector.
9.8.1 Modem Setup - Initialization String
The Universal Monitor has an on-board modem that offers dial-up access to all LCD functions as well
as features available only through the Service Terminal Interface (see A.1 - Comparison of Func-
tions: LCD and Service Terminal Interface). The modem also permits remote notification of
alarms.
Supported Modem Settings
Supported settings vary for different types of access:
Default Modem Settings
Table 27 shows the default settings for modem options.
Configuring the Modem
To configure the modem:
Log In and Choose Setup System
1. From the Main Menu, use the arrows
1. From the Main Menu, use the arrows
↑ ↓
to
choose System and
Control, then press Enter ↵ (see 9.1 - Login for help).
2. Enter your password at the Login screen.
3. From the System and Control Menu, use the arrows
3. From the System and Control Menu, use the arrows
↑ ↓
to
choose
Setup System, then press Enter ↵ .
Table 26
Supported modem settings
For:
Modem supports:
Dial-up via terminal
9600 baud, no parity, 8 data bits, 1 stop bit
Pager access
9600 baud, even parity, 7 data bits, 1 stop bit and TAPI protocol version 1.8
International
dialing
For calls involving countries that do not support country code B5 (see Table 28):
• Modem model MT5600SMI is required (model number is on the modem label).
• +GCI=xx (xx is the country code) must be added to the initialization string (see Step 7 in
• Modem model MT5600SMI is required (model number is on the modem label).
• +GCI=xx (xx is the country code) must be added to the initialization string (see Step 7 in
this section).
Table 27
Default settings - modem
Feature
Default
Other Options
Initialization String (Init String)
ATS0=1
Any string (up to 40 characters); for international dialing,
add +GCI=xx, where xx is the country code (except B5
countries—see Table 28)
Enable Modem Diagnostic Messages
N (disable)
Y (enable)
Modem Dial Prefix
ATE0X4DT
Any string
Modem Hang Up Delay After a Call
10 seconds
Any number (up to 99 seconds)
Setup System Menu
SETUP INPUT
SETUP COMMON ALARM
SETUP SENSOR
SETUP I/O MATRIX
SETUP COMMON ALARM
SETUP SENSOR
SETUP I/O MATRIX
↑ ↓=NEXT
↵
=SELECT
SETUP OUTPUT
> SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD
SETUP EXP BOARD