PLANNING YOUR INSTALLATION
PAGE 4
LOCAL AND NATIONAL CODE REQUIREMENTS
The installation of these appliances must conform with
local codes or, in the absence of local codes, with the
National Fuel Gas Code, (for USA) NFPA 54 / ANSI
Z223.1-latest edition.
Air Circulation Blower: The blower electrical power
cord must be electrically grounded per local codes or
per electrical codes:
In USA, NEC, ANSI / NFPA 70-1987.
In Canada, CSA C22.1
WARNING
Electrical Grounding Instructions. This ap-
pliance is equipped with a three-prong
(grounding) plug for your protection against
shock hazard and should be plugged di-
rectly into a properly grounded three-prong
receptacle. Do not cut or remove the
grounding prong from this plug.
WARNING: To avoid electrical shock, always ensure
that the power cord is unplugged (i.e., there is no elec-
trical power to the circulation blower) before handling
the circulation blower or performing any work on the
appliance.
High Altitude: Gas inputs shown are for elevations up
to 4500 feet.  For elevations above 4500 feet, contact
your gas supplier or qualified service technician re-
garding the necessary deration of appliance (deration:
replacing burner orifice with a smaller one to reduce
input). Ratings must be reduced at the rate of 4 percent
for each 1,000 feet above sea level. Refer to (for USA)
NFPA 54 / ANSI Z223.1-latest edition for orifice resiz-
ing.
TOOL / EQUIPMENT LIST
The following tools and equipment are recommended
for completing the partial assembly required when the
appliance is installed:
 
7/16”, 3/4” open end wrenchs.
 
1/4”, 3/8” nut drivers.
 Pipe 
wrench.
 
Phillips head screw driver.
 Flat 
head 
screwdriver.
 
Pipe sealant compound.
 
Leak test fluid“U” tube manometer or pressure gauge (0 -
16” (inches water column) H2O scale.
GAS PRESSURE (WC = Water Column)
Minimum inlet gas supply pressure for the purpose
of input adjustment:
Natural Gas - 4.5” WC min. – 7.0” WC max.
Propane (LP) - 11” WC min - 13.0” WC max.
Manifold gas supply pressure:
LOW
HIGH
Natural Gas -   1.8” + / -.3” WC    (to)    3.5” + / -.3” WC
                        25,000 BTU / hr             37,000 BTU / hr
Propane (LP)   6.6” + / -.3” WC     (to)   10” + / -.3” WC
                        28,000 BTU / hr             35,000 BTU / hr
Note: ” WC = Inches Water Column
PRESSURE TAPS
Gas Inlet Pressure Tap - Located on bottom left of gas
valve.
Gas Outlet (manifold) pressure tap - Located on bottom
right of gas valve.
Gas Control Valve
Pressure Testing: See Pressure Testing on page 8.