RC3000 Antenna Controller 
Chapter 2 
Installation 
 
 61  
The azimuth scale factor is obtained by noting the difference in the azimuth pointing solution angles 
between two satellites and the pulse counts when on the satellites.  For best results, use satellites that 
are as far apart as possible and make sure you have positively identified the satellites. 
Example : Kansas City (38’56N,94’45W)  heading of 180.0 
SATELLITE AZIMUTH 
POINTING 
SOLUTION ANGLE 
PULSE 
COUNT 
SPACENET 2 (69.0W) 
-37.5 
33333 
SATCOM C5 (135.0W) 
53.4 
11000 
Difference 90.9 
22333 
(22333 / 90.9) * 57.29 = 14075 pulses/radian 
SCALE FACTOR FOR RESOLVER SYSTEMS 
The RC3000 uses the actual digitized resolver count in the same way it uses a pulse count.  The RC3000 
utilizes a 16 bit resolver to digital converter which generates a count value from 0 to 65,535.  Typically the 
resolver sensor rotates with the antenna.  The resulting “pulse scale factor” therefore is: 
65536 reslover counts / ( 360 degrees * 1 radian/57.29 degrees) = 10430.2 “pulses” / radian 
The default scale factor for a resolver system is therefore rounded up to 10431. 
The constants are entered via the azimuth pulse drive (3.3.1.7) and elevation pulse drive (3.3.1.10) 
configuration item screens.