Water quality requirements  30 
Water quality requirements 
Water quality requirements and specifications 
 
Closed-loop water must not contain any lime scale deposits or loose debris. 
 
The water must have a low level of hardness, particularly a low level of carbon hardness. 
Additionally, the water must not be so soft that it attacks the materials with which it comes into 
contact. 
 
The chilled water temperature to be supplied to the HP POD is 12º to 24ºC (55º to 75ºF). Freezing 
water might cause a blockage and damage to the unit. In outside locations subject to freezing 
temperatures, an additive such as glycol might be necessary to lower the freezing point. However, 
the heat transfer potential of the water is lower, so the equipment must be derated properly. 
 
Acceptable water quality specifications 
Water must be maintained per the following acceptable water quality standards. 
 
Parameter Range 
pH 8.0–10 
Specific conductance at 25ºC 
(77ºF) 
0–2500 µmhos/cm 
Alkalinity ("M" as CaCO
3
) 150–1000 
ppm 
Sulfur (SO
4
) 0–150 
ppm 
Chloride (Cl) 
0–100 ppm 
Hardness (CaCO
3
) 0–350 
ppm 
Calcium hardness (CaCO
3
) 0–200 
ppm 
Magnesium hardness (CaCO
3
) 0–150 
ppm 
Copper (Cu) 
< 0.20 ppm 
Iron (Fe) 
< 3.0 ppm 
Aluminum (Al) 
< 0.50 ppm 
Sodium (Na) 
0–1000 ppm 
Silica (SiO
2
) 0–150 
ppm 
Zinc (Zn) 
< 1.0 ppm 
Manganese (Mn) 
< 0.1 ppm 
Phosphate Ortho- (PO
4
)  
< 3 ppm 
Bacteria 
< 1000 CFU/ml 
Suspended solids 
< 10 ppm 
 
If your water is out of range, consult a water quality expert.