Maintenance 54 
Maintenance 
Periodic maintenance 
Perform periodic inspections of the POD to ensure there is no sign of overheating. During periodic 
inspections, pay special attention to electrical connections and wiring. 
 
Electrical busway maintenance 
Periodically tighten the electrical busway connections. HP recommends tightening the electrical busway 
connections every six months. 
Inspect the busway drop boxes for loose connections, and tighten if necessary. 
 
Water system maintenance 
HP does not maintain your water system quality.  
Consult a water treatment specialist to perform the following maintenance: 
Flush the HP POD 
How often you must flush the HP POD depends on how often you shutdown the HP POD and the water 
quality. 
Maintain water quality 
The water treatment specialist should periodically take a water sample and add new chemical treatments 
to the HP POD water or water distribution kit as needed to maintain the specified water quality ("
 
Air filter replacement 
There are twelve 14 in x 36 in x 1 in air filters inside the HP POD. 
If you have the optional air filter sensor (on page 
) installed, you will be notified through your BMS 
when you need to change a filter.  
If you do not have the sensor installed, HP recommends periodically inspecting and changing each air 
filter. 
 
Air and water heat exchanger maintenance 
The air and water heat exchanger requires no maintenance. If particulates are present in the cooling 
water, a filter must be fitted immediately upstream from the water inlet fittings. Check the functionality of 
the condensation drainage system regularly. Regularly perform visual inspections for leaks (annually).