HP Performance Optimized Data Center (POD) 40cp Manuale Di Servizio

Pagina di 79
 
Illustrated parts catalog  13 
Aisle clearances 
Cold aisle clearance 
The maximum protrusion of any installed IT component directly impacts the available cold aisle clearance for 
removal and replacement of other IT components. Maximum component depth must follow the clear aisle 
distance calculations. The following figure shows how to calculate this distance. 
 
The maximum rack face-to-cold aisle wall distance is 39.5 inches. In the figure, X represents any protrusion 
into the cold aisle starting from the rack face of the installed IT component (for example, the bezel). Y 
represents cold aisle clearance. The cold aisle clearance dictates the maximum depth (D) of any installed IT 
component. To find the maximum cold aisle clearance, calculate 100.33 cm (39.5 in) - X = Y. 
   
 
IMPORTANT:
  As the value for X increases, the value for Y decreases, which also decreases the 
maximum depth allowed for an installed component.