HP Performance Optimized Data Center (POD) 40cp Manuale Di Servizio

Pagina di 79
 
Periodic maintenance  66 
Component to be inspected 
Task 
Frequency 
Capable Party 
Circuit breakers 
Panel breaker operational test 
(open and shut). 
Annually 
Licensed electrician 
— 
LLS inspection of breakers, 
disconnects, motor starters, and 
fuse holders (physical). 
Quarterly 
Licensed 
electrician/Qualified 
personnel 
— 
Breaker fault testing for all 
breakers ≥ 250AF 
Every 3 years 
Third party testing 
facility 
Sensors 
Verify proper operation of: 
 
Internal POD temperature 
sensors (thermometer) 
 
Relative humidity sensors (RH 
meter) 
(Investigate discrepancies, trouble 
shoot, and replace as necessary.) 
Annually 
Qualified personnel 
— 
Compare the following with site 
indications (if available): 
 
CWS/CWR temperature 
 
CWS/CWR pressure 
 
Flow rate (if possible) 
(Investigate discrepancies, trouble 
shoot, and replace as necessary.) 
Annually 
Qualified personnel 
— 
POD SHUT DOWN REQUIRED 
Calibrate (zero out) POD 
differential pressure sensors. 
(Investigate discrepancies, trouble 
shoot, and replace as necessary.) 
Annually 
Qualified personnel 
Lighting 
Visual inspection of lighting 
fixtures and lamps. Replace 
components upon failure. 
As needed or 
Quarterly 
Licensed electrician/ 
Qualified personnel 
 
 
Fire alarm and suppression system 
 
Component to be inspected 
Task 
Frequency 
Capable Party 
Full system functional check 
Inspect and perform a functional 
check of the system 
As required by 
local code 
Authorized technician 
Fire panel 
Inspect and test fire panel 
battery backup system 
Every 2 years 
Authorized technician 
VESDA 
Inspect and test VESDA power 
supply 
Quarterly 
Authorized technician 
— 
Inspect the VESDA pipe network  Every 2 years 
Authorized technician 
— 
Inspect the VESDA filter. 
Replace as necessary 
Annually 
Qualified personnel 
— 
Conduct a VESDA pipe integrity 
smoke test 
Annually 
Authorized technician 
— 
Check the VESDA pipe flow 
Annually 
Authorized technician 
— 
Clean the VESDA sampling 
points 
Every 2 years 
Authorized technician 
— 
Flush the VESDA pipe network  Every 2 years 
Authorized technician 
— 
VESDA system air 
sampling/smoke test 
As required by 
local code 
Authorized technician