DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Specifications
Page 179
Communications
Supported Communication Methods
Type
Function
PC Configuration Socket
Direct configuration using the PC Configuration Software
RS485
Configuration and general communications using Modbus RTU.
Ethernet
Configuration and general serial communications using the Modbus 
TCP protocol.
USB
Upload/download of configuration/profile files from the PC Software 
or other instruments and download for Data Recordings.
PC Configuration Socket
Type:
RS232 Serial Communications
Connection
PC Configurator Cable to RJ11 socket under case.
Isolation:
Not isolated from input or SSR Driver outputs. For bench 
configuration only. 
CAUTION:
Not for use in live applications.
RS485
Type:
RS485 Asynchronous Serial Communications Module.
Connection
Locates in Option Slot A.
Connection via rear terminals (refer to wiring diagram).
Protocol:
Modbus RTU Slave or Modbus RTU Setpoint Broadcast Master.
Slave Address Range:
1 to 255. 
Bit rate:
4800, 9600, 19200, 38400, 57600 or 115200 bps.
Bits per character:
10 or 11 (depending on parity setting) plus 1 Stop Bit
Parity:
None, even or odd (selectable).
Isolation:
240V reinforced safety isolation from all inputs and outputs.
Ethernet
Type:
Ethernet Communications Module.
Connection
Locates in Option Slot A.
Connection via RJ45 connector on top of case.
Protocol:
Modbus TCP Slave only.
Supported Speed:
10BaseT or 100BaseT.
IP Address Allocation:
Via DHCP or manual configuration via PC Tool.
Isolation:
240V reinforced safety isolation from the supply, inputs and outputs 
(except SSR Drivers).
USB Socket
Targeted Peripheral:
USB Memory Stick.
Connection
Locates in Option Slot C. Connection via front mounted connector.
Protocol:
USB 1.1 or 2.0 compatible. Mass Storage Class.
Isolation:
Reinforced safety isolation from all inputs and outputs