Honeywell DVD Recorder L Manuale Utente

Pagina di 36
R7140G,L,M BURNER CONTROL MODULES
66-1153—03
6
a
 30 seconds with JR2 clipped and jumper from terminal 8 to terminal 15.
*
 STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A purge card is selected; 15 timings are available from 2 seconds to 30 minutes.
NOTE: Allowable inrush can be up to ten times the pilot 
duty rating.
EXAMPLE: Pilot duty rating = 50 VA.
At 120 V, running current is:
50/120 = 0.42A.
Maximum allowable inrush is ten times 0.42A = 4.2A.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and marked 
on the product to make sure the product is suitable for 
the application.
3. Installer must be a trained, experienced, flame 
safeguard service technician.
4. After installation is complete, check out the product 
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury, 
or death.
To prevent possible hazardous burner operation, verify 
safety requirements each time a control is installed on 
a burner.
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect the power supply before beginning 
installation. More than one power supply disconnect 
may be required.
IMPORTANT
1. Wiring connections for the relay modules are unique; 
therefore, refer to Fig. 4–11 or the correct 
Specifications for proper subbase wiring, and 
sequence charts.
2. Wiring must comply with all applicable codes, 
ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) 
wiring.
4. Loads connected to the R7140 must not exceed 
those listed in the Specifications; see Table 3 and 4.
5. Limits and interlocks must be rated to simultaneously 
carry and break current to the ignition transformer, 
pilot valve, and main fuel valve(s).
6. All external timers must be listed or component 
recognized by authorities who have jurisdiction for 
the specific purpose for which they are used.
7. For on-off gas-fired systems, some authorities who 
have jurisdiction prohibit the wiring of any limit or 
operating contacts in series between the flame 
safeguard control and the main fuel valve(s).
8. Two Flame Detectors can be connected in parallel 
with the exception of flame detectors C7927, C7915, 
C7961, and C7962.
9. This equipment generates, uses and can radiate 
radio frequency energy and, if not installed and used 
in accordance with the instructions, may cause 
interference to radio communications. It has been 
tested and found to comply with the limits for a 
Class A computing device of Part 15 of FCC rules 
which are designed to provide reasonable protection 
against such interference when operated in a 
commercial environment. Operation of this 
equipment in a residential area may cause 
interference; in which case, the users at their own 
expense may be required to take whatever measures 
are required to correct this interference.
10.This digital apparatus does not exceed the Class A 
limits for radio noise for digital apparatus set out in 
the Radio Interference Regulations of the Canadian 
Department of Communications.
Table 5. Sequence Timing for Normal Operation.
Device Initiate Standby Purge
Flame 
Establishing 
Period
Run
Post 
Purge 
Timing Interlock Circuits
Firing 
Rate 
Circuit
Energy 
Saving 
Pre-Purge
Approval 
Code 
Bodies
Pilot
Main
R7140G 10 sec.
*
**
4 or 10 
sec.
10, 15 
sec.
a
 or 
intermittent.
*
15 sec. Pre-Ignition, 
Running, Low Fire
4-wire 
modulating
No
UL/CSA 
Modulating
R7140L
10 or 15 
sec.
a
Pre-Ignition, 
Lockout High and 
Low Fire
FM/IRI 
Modulating
R7140M
10 sec. or 
intermittent
Pre-Ignition, 
Running, isolated 
Low Fire.
2-wire 
isolated 
On-Off-On 
contacts
UL/CSA 
On-Off.