Harris Performance 6800 Manuale Utente

Pagina di 76
 Chapter 9: 6801PS-48 Power Supply Module
Installing the 6801PS-48
40
6800/7000 Series - Frames and Power Supplies  Installation and Operation Manual
Installing the 6801PS-48
Precautions
To reduce the risk of electric shock or energy hazards, heed the following 
cautions: 
• Connect the 6801PS-48 to a reliably grounded SELV source or a 
centralized DC source.
• The branch circuit overcurrent protection must be rated a 
maximum 10 A circuit breaker in series with a maximum 5 A 
listed fuse. (
See 
suggested protection devices on page 41.)
• Use 14 AWG solid copper conductors only.
• A readily accessible disconnect device that is suitably approved 
and rated, shall be incorporated into the field wiring. (
See 
suggested breaker switch type on page 41.)
• To be installed in a restricted access area in accordance with the 
NEC or the authority having jurisdiction.
To reduce the risk of electric shock, heed these cautions:
• Perform installation and exchange only if you are a trained 
technician who is familiar with these instructions and aware of 
the shock hazards of working with live equipment.
• Install the 6801PS-48 power supply in accordance with the 
schematic diagram shown on page 41
• Power can only be disconnected completely from the 6800/7000 
series frame through a studio installed breaker or fuse.