 Chapter 10: 6804PS-1-48 Power Supply Module
Installation
44
6800/7000 Series - Frames and Power Supplies Installation and Operation Manual
Installation
Precautions
To reduce the risk of electric shock or energy hazards, heed the following 
cautions:
Connect the 6804PS-1-48 to a reliably grounded SELV source or 
a centralized DC source.
The branch circuit over-current protection must be rated a 
maximum 10 A circuit breaker in series with a maximum 5 A 
listed fuse. (See suggested protection devices page 45.)
Use 14 AWG solid copper conductors only.
A readily accessible disconnect device that is suitably approved 
and rated, shall be incorporated into the field wiring. (See 
suggested breaker switch type on page 45.)
To be installed in a restricted access area in accordance with the 
NEC or the authority having jurisdiction.
To reduce the risk of electric shock, heed the following cautions: 
Perform installation and exchange only if you are a trained 
technician who is familiar with these instructions and aware of 
the shock hazards of working with live equipment.
Install the 6804PS-1-48 power supply in accordance with the 
schematic diagram shown onpage 45. 
Power can only be disconnected completely from the 6800/7000 
series frame through a studio installed breaker or fuse.
Connect this equipment to a 48 VDC source that is electrically 
isolated from the AC source. The 48 VDC source must be 
reliably connected to earth.