FLOOR PROTECTION
A combustible fl oor must be protected by non-combustible material (like tile, concrete board, or certifi ed to UL-1618 or as defi ned by local codes) 
extending beneath the heater and a minimum of 6" from each side and minimum 18" from the front face of the stove and minimum 6" (or the rear 
clearance to combustibles whichever is smaller) from the rear of the stove. 
When installed with horizontal venting, non-combustible fl oor protection must beneath the fl ue pipe and extend 2" (51mm) beyond each side.
NOTE:  In  Canada,  fl oor protection must 
extend 18" (450mm) to the front 
and 8" (200mm) to each side and 
back of the stove.
   Minimum Overall Depth (Y) of Floor Protector
 
                     Residential                           Residential                      Mobile Home                    Alcove
                         Unit                             "C" Vent                          Close Clearance               Close Clearance
                                                          
 
                   Y                    Z 
                  Y  
          Z 
                Y                     Z 
   Z
   H300 (US) 
              44-1/2"          6" (152 mm)         44-1/2"       6" (152 mm)            44-1/2"      6" (152 mm)        44-1/2"    6" (152 mm)
 
            (1130 mm)  
           (1130 mm)                              (1130 mm)               
        (1130 mm)                            
   H300 (Canada)   
             46-1/2"           8" (203 mm)         46-1/2"       8" (203 mm)            46-1/2"      8" (203 mm)        46-1/2"    8" (203 mm)
 
            (1181 mm)  
           (1181 mm)                              (1181 mm)               
        (1181 mm)                             
INSTALLATION
IF SIDE LOAD DOOR IS USED:
Floor protection must extend 18" (457mm) 
from the side of the unit to the wall.
Floor protection must be a minimum of 3/8" 
thick with a minimum k factor of 0.84.
  
Minimum Overall Width (X) of Floor Protector
 for all installations: 
  H300 39" 
(990 
mm) 
US
  
43" 
(1092mm) 
Canada