CHAPTER 2: INSTALLATION
WIRING
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
2–15
FIGURE 2–3: LM10 Control Signal Contacts
Service hint: Remove the bottom terminal block first, using a small screwdriver in either
end. The top terminal block can then be removed using a coin or any broad-blade tool.
end. The top terminal block can then be removed using a coin or any broad-blade tool.
2.1.4
Sensor Pack Input
Connectors S1 and S2 are used to connect to all CT Sensor Packs. 5 A CTs connect via the
Phoenix terminal block.
Phoenix terminal block.
2.1.5
Wiring Diagram
A typical LM10 wiring diagram is shown below. The relay should be programmed as
“Maintained Off” (under “Other Settings”) for momentary start input. See page 4–34 for
additional details.
“Maintained Off” (under “Other Settings”) for momentary start input. See page 4–34 for
additional details.
S1/S2 Pins
Description
1
CT phase A
2
CT phase B
3
CT phase C
4
CT phase A common
5
CT phase B common
6
CT phase C common