CHAPTER 4: FUNCTIONALITY
CONFIGURATION SETTINGS
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–29
4.2
Configuration Settings
4.2.1
Overview
An overview of the LM10 programmable parameters is shown below.
Table 4–1: LM10 Programmable Parameters
Parameter
Range/Options
Default
Reference
Control power transformer
CPT ratio
200:120, 240:120, 480:120, 600:120, 
2400:120, 3000:120, 3300:120, 
4200:120, 4800:120, 5400:120, 
6000:120, 7200:120
240:120
Current transformer
CT / sensor pack
27 A Sensor Pack, 90 A Sensor Pack, 
75:5, 100:5, 150:5, 200:5, 225:5, 
250:5, 300:5, 400:5, 500:5, 600:5, 
700:5, 800:5
100:5 Ratio
CT turns
1 to 4 in steps of 1
1
Starter type
FVNR, FVR, RV, 2S1W, 2S2W, Custom
FVNR
FLA (RUN1 and RUN2)
1.2 to 800 A in steps of 0.1
100.0 A
Ground fault level
0.4 to 20 A in steps of 0.2 or Off
Off
Ground fault timeout
0 to 2.5 seconds in steps of 0.1
0.5 sec.
Jam level
100 to 250% of FLA in steps of 1 or 
Off
Off
Jam timeout
0 to 1000 seconds in steps of 5
120 sec.
Stall level
330 to 600% of FLA in steps of 5 or 
Off
Off
Stall timeout
0 to 30 seconds in steps of 0.5
10 sec.
Current unbalance level
2 to 25% of FLA in steps of 1 or Off
Off
Current unbalance 
timeout
0 to 255 seconds in steps of 1
5 sec.
Load loss level
15 to 100% of Full Load in steps of 1 
or Off
Off
Load loss timeout
0 to 255 seconds in steps of 1
60 sec.
Undervoltage
96 V fixed (trip delay time 0.5 sec.)
96 V
Overvoltage
140 V fixed (trip delay time 0.5 sec.)
140 V
Aux. sense 1 time delay
Aux. sense 2 time delay
0.1 to 25.0 sec. in steps of 0.1 for ON 
state; 0.0 sec. for Disabled
0.4 sec.
Run 1 to Run 2 time delay; 
Run 2 to Run 1 time delay
0 to 600 seconds in steps of 1
0 sec.
Under/overvoltage enable
Off, On
On
Maintained input switches
Off = momentary,
On = maintained/latched
Off
Auto restart
Off, On
Off