4–38
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETTINGS
CHAPTER 4: FUNCTIONALITY
Entering a passcode at the 
Pass Code, Login
 screen will change the login indicated by an 
asterisk at the end of the line. The default passcode is “0”. You must be logged in as 
“Config” to be able to change the passcode. The green power LED will flash while logged in 
as configurator. The unit will stop any run relay when in configuration mode. The LM10 
must be returned to user mode before beginning normal operations.
Once the passcode is changed, the PDU will retain it in memory and will automatically 
login when the CONFIG button is held/pressed upon plugging in the RJ11 connector or on 
power up. This is handy when using a hand held PDU for multiple relay program changes.
4.2.11 Run Operations
PATH: Configuration 
ØØØØØØØØØ
 Run Operations
Input terminal 21 selects how the run command is controlled. If power is applied to the 
relay, then the network has run control. If not the hard-wired switches control. Note that a 
PDU logged in for configuration will disable run commands from both DeviceNet and hard-
wired switches.
With DeviceNet fault enabled and scanner connections not yet established, switching to 
DeviceNet will cause the DeviceNet fault and stop any run condition of the LM10. Hard-
wired Stop will always have priority. If stop terminal 3 is powered, the LM10 will not run.
4.2.12 Factory Default
PATH: Configuration 
ØØØØØØØØØØ
 Factory Default
Select “Yes” to restore the factory values.
Configuration
Run Operations „
Factory default
Run Operations
Run 1
Range: Run 1, Run 2, Stop
Configuration
Factory deflt „
Factory Default
No
Range: No, Yes