CHAPTER 5: COMMUNICATIONS
DEVICENET OPERATIONS
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5–47
The Hi and Lo bytes of the phase current A, B and C are reversed as compared to poll group 1 to make 
it compatible with the format of Firmware revision 1.40 polling data.
This data group also can be retrieved via explicit messaging to the assembly object class 4, instance 
105, attribute 3.
UINT = 16 bit unsigned integer.
See Data Formats on page 5–57 for details on the F20, F21, and F22 data formats.
5.1.3
Identity object
Identity Object, Class Code 1, Services:
Identity Object, Class Code 1, Attributes:
Identity Object, Class Code 1, Instance 1, Attributes:
5.1.4
Message Router
The message router (Class Code 2) object provides a messaging connection point through 
which a client may address a service to any object or instance residing in the physical 
device. There is no external visible interface to the message router object.
5.1.5
DeviceNet Object
DeviceNet Object, Class Code 3, Services:
DeviceNet Object, Class Code 3, Attributes:
Code
Name and Description of Services Available to this Object
0x05
Reset: Reset the device to power up configuration
0x0E
Get_Attribute_Single: Returns the contents of the given attribute
Attribute
Access
Name/Description
Data Type
Value
none
---
---
---
---
Attribute
Access
Name/Description
Data Type
Value
1
Get
Vendor
UINT
928
2
Get
Device type
UINT
22
3
Get
Product code
UINT
77
4
Get
Revision (major, minor)
BYTE[2]
0x013C
Code
Name and Description of Services Available to this Object
0x0E
Get_Attribute_Single: Returns the contents of the given attribute.
0x4B
Allocate: Creates predefined M/S connections.
0x4C
Release: Deletes predefined M/S connections.
Attribute
Access
Name/Description
Data Type
Value
1
Get
Revision
UINT
2