Energy Tech Laboratories MR212 Manuale Utente

Pagina di 28
 
12
Maxitrol M511 and M611 
Low Fire Bypass Screw 
Mod Valve Voltage Summary 
Volts DC 
Firing Mode 
0 to 5 VDC 
Low Fire 
5 to 15 VDC 
Modulation 
15 to 20 VDC 
High Fire 
Maxitrol MR212 Low 
Fire Bypass Screw 
Average Manifold Pressure vs. Firing Rate/Ft. of Burner
-1.00
0.00
1.00
2.00
3.00
4.00
5.00
6.00
0
100000
200000
300000
400000
500000
600000
Firing Rate (BTU/Hr/Ft. of Burner)
M
an
if
o
ld
 P
ressu
re
 (i
n
. w
.c.
)
Natural Gas
Propane Gas
Main Burner Adjustment
 
1.  Once the pilot has been properly established, the 
manifold gas pressure or temperature rise should be 
adjusted to jobsite conditions.  The gas pressure 
regulator (integral to the combination gas control on size 
1-3 heaters and located in the modulating valve on size 
4-5 heaters) is adjusted at the factory for average gas 
conditions.  It is important that the gas be supplied to the burner in accordance with the input 
rating on the rating plate.   
2.  Create a high fire call for heat.  This should be done with the blower on and all gas controls on.  
High fire can be achieved by removing the wire at terminal #4 (remove wires #2 and #4 for 
Maxitrol 44 systems) from the Maxitrol 14 amplifier.   
3.  The manifold pressure should be checked 
at the pressure tap downstream of the 
modulating valve.  The graph to the right 
indicates the proper manifold pressure for 
the desired amount of BTUs per foot of 
burner. For natural gas systems, the high 
fire manifold pressure should not exceed 
in. w.c.  
For propane gas, the high fire 
manifold pressure should not exceed 2.5 
in. w.c.  
Another method of checking high 
fire is to measure the temperature rise of 
the unit.  The temperature rise should be 
set to design conditions and typically is 
minimum 70°F.   
4.  Remove the cap from the combination gas 
valve regulator adjustment (size 1-3) or 
the cap from the MR212 valve (size 4-5).  
Using the regulator pressure adjusting screw, adjust the high fire manifold pressure to 5 in. w.c. 
maximum for natural gas and 2.5 in. w.c. maximum for propane gas.  High fire should be set to 
generate the desired temperature rise.  If the high fire screw is at the end of its adjustment and 
more pressure is needed, then adjust the main building gas pressure regulator spring (located 
external to the unit) to achieve the proper manifold pressure.  Turning the regulator screw 
clockwise will increase pressure and counter-clockwise will decrease pressure.  Remember - 
The high fire DC voltage should read 12 VDC minimum and should typically be 15 VDC on 
the Flame Safety Controller test jacks.
  
5.  Reconnect the wire on the Maxitrol 14 amplifier at terminal #4 (wires #2 and #4 for Maxitrol 44).  
6.  The low fire manifold pressure must now be set.  Low fire can be achieved 
by removing the wire at terminal #5 from the Maxitrol 14 amplifier (remove 
#8 for Maxitrol 44).  Check the low fire flame signal to ensure that the DC 
voltage is 12 VDC minimum 
on the Flame Safety Controller test jacks. 
7.  Using the bypass screw (located on the side of the M511 and M611 valves, 
and under the cap of the MR212 valve), adjust low the low fire manifold 
pressure until there is a very thin flame along the entire length of the burner.  
No dark spots should be seen in the burner.  The burner may be observed 
through the view-port located on the external wall of the heater.  Replace 
the cap to the Maxitrol valve and restore all of the original wiring on the 
Maxitrol amplifier and gas components. 
8.  A final gas leak check shall be performed to verify the gas-tightness of the 
heater’s components and piping under normal operating conditions.  This 
can be done by measuring the gas pressure at the ¼” gas plug just 
downstream of the modulating valve.