Energy Tech Laboratories MR212 Manuale Utente

Pagina di 28
 
16
Flame Safety Controller 
 
Air Flow Switch 
DC Flame Signal 
DC Voltage 
Flame Status 
0 to 5 VDC 
No Flame 
6 to 11 VDC 
Weak Flame 
12 to 18 VDC  Strong Flame 
Sequence of Operation 
The direct-fired heater is most easily understood when broken down into smaller individual systems. 
There are two main systems, a make-up air fan and a heater. The make-up air fan consists of a blower 
and motor. The heater may be further broken down into two control systems, the Flame Safety Control 
(FSC) and the Modulating Gas System (MGS). The burner mixes air with the gas (Natural or LP) which 
heats the air. 
Flame Safety Control
 
The first system to understand is the Flame Safety
 
Control. The FSC 
is there only  to monitor the flame, NOT to control temperature. The 
FSC uses a flame rectification sensor mounted on the pilot assembly 
to detect the presence of flame in the burner.  Flame strength and 
presence can be measured at the FSC by reading the rectified flame 
signal.  This is done by using a DC voltage meter attached to the test 
jacks on the top of the control.  Flame is present when the DC voltage 
reads between 6 and 18 VDC.  Ideal flame intensity produces a signal 
of  12 VDC or greater.  The FSC is also wired into an airflow switch, 
which tells it whether there is proper airflow through the unit (not just 
any airflow, but proper airflow). Proper airflow occurs when there is a 
.15 in. w.c. to .80 in. w.c. differential pressure drop across the 
burner
.   When the airflow through the heater produces a pressure 
drop in this range, the FSC indicates so by illuminating the AIRFLOW 
LED.  The FSC controls the opening of the redundant solenoid gas 
valves and the operation of the spark igniter to initiate a pilot flame 
upon start-up. 
 
The  OPR CTRL LED indicates that there is power to the FSC. Next, 
the AIRFLOW LED will come on if there is proper airflow through the 
unit.  Third, the unit will pause to purge any gasses or combustible vapors before attempting flame 
ignition. Then, there is a Pilot Trial For Ignition (PTFI) and the PTFI LED comes on. During PTFI, the FSC 
opens the pilot gas valve and allows gas to flow to the pilot assembly.  At the same moment, the spark 
igniter is started, causing the spark to ignite the pilot gas.  When the flamerod sensor detects the flame, it 
turns on the FLAME LED, turns off the PTFI LED, and powers the modulating gas system.  This is the 
normal operating mode. The FSC continues to monitor the flame and airflow.  Once this occurs, the unit is 
in a main flame cycle and thus powers the main gas valve and the modulating gas system.  This is the 
normal operating mode. The FSC continues to monitor the flame and airflow.  The last LED on the FSC is 
the ALARM LED.  This will turn on when the FSC determines an unsafe condition has occurred, and will 
not allow the unit to recycle for heat until it has been properly reset.  Anytime the FSC has gone into 
“Alarm” mode, the problem must be diagnosed and corrected to avoid future lockouts after resetting.  To 
begin troubleshooting, or to reset the FSC, shut down power to the heater and restart the heater.  This 
will clear the alarm from the flame safety. 
Air Flow Switch
 
There are both high and low airflow switches contained within one housing 
measuring the pressure drop across the burner.  This is to insure that there is 
proper airflow (.15 in. w.c. to .80 in. w.c.) across the burner and proper 
combustion at all times.  Both switches are wired in series and have single pole 
double throw (one common contact, one normally open contact, and one normally 
closed contact) switches that are ‘switched’ by air pressure. There are two airflow 
tubes in the heater, located near the burner and profile plate assembly (profile 
plates surround the burner and control air into the burner section).  In the case of 
clogged filters, blocked intake, excessive duct static pressure, or a broken belt, the 
correct burner differential pressure may not be achieved, not allowing the low