The following image and list outlines the typical direct fired heater components and their functions. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1.  Gas Inlet – Main gas supply connection 
2.  Motor Starter – Contactor with overload protection to start and protect motor. 
3.  Freeze-Stat Thermostat (Optional) – De-energizes blower motor if the discharge air 
temperature falls below the set point. 
4.  Cooling Interlock Relay (Optional) – Energizes power to cooling circuit on call for cooling. 
5.  Inlet Gas Pressure Tap – Inlet gas pressure should be measured here. 
6.  Combination Gas Valve - A combination of redundant solenoid valves, pilot valve and gas 
regulator built into one unit. 
7.  Pilot Tubing – Pilot tube connection to combination gas valve. 
8.  Manual Reset High Temperature Limit – Safety device that prevents the heater from 
overheating.  
9.  Maxitrol Modulating Amplifier - Regulates temperature by modulating gas valve 
10.  Power Transformer – Installed when motor voltage > 120V.  Used to provide 120V service to 
controls. 
11.  Circuit Breaker – Protects electrical components from high current spikes. 
12.  Terminal Strip – Central location to terminate control wiring.  Should be used for troubleshooting. 
13.  Control Transformer – 120V primary; 24V secondary control transformer. 
14.  Low Pressure Airflow Probe – Measures profile pressure downstream of burner. 
15.  High Pressure Airflow Probe – Measures profile pressure upstream of burner. 
16.  Modulating Gas Valve – Modulates gas flow to burner to provide proper air temperature. 
17.  Manifold Gas Pressure Tap – Manifold gas pressure should be measured here. 
18.  Flame Safety Control – Initiates and monitors flame. 
19.  Airflow Switch – A safety device insuring proper air flow during burner operation. 
20.  Ignition Transformer – Produces high voltage spark to ignite flame. 
21.  Intake Air Thermostat – De-energize heating circuit when intake air exceeds set-point. 
22.  Damper Actuator – Motor containing end switch that opens intake damper. 
23.  Manual Gas Shut-Off Valve Allows gas flow to burner to be shut off to leak test gas train 
10 
15 
16
20
22
23
12
14
19
18 
21
13
17
11