Problem
Possible Cause
Solution
The fan is not 
operating
- No power to the fan
- Check the power supply wires in the junction box by the fan.
- Check the circuit breaker.
- Check that the fan is actually turned on.
The fan is not running 
at full speed and/or is 
humming
- The capacitor is 
improperly connected 
or not connected at all 
(RSIB 300 only)
- Check the connections inside the junction box. The capacitor must be installed 
according to the wiring diagram.
The fan is rotating 
backwards (except 
RSIB 300)
Phase sequence in 
the power to the fan is 
reversed
- Swap two phases in the junction box.
The fan is vibrating 
vigorously
- A transportation 
device has not been 
removed.
- Foreign matter is 
stuck in the impeller.
- A ball bearing is 
damaged.
- A balancing weight 
has fallen off impeller
- Remove the transportation device.
- Turn off the fan and remove the foreign matter.
- Turn the fan off. After the motor has stopped revolving, spin the impeller and listen 
for a grinding noise from the motor. If necessary, replace bearing or entire motor.
- Re-balance impeller or replace it. Check motor for damages.
The fan stops in the 
middle of firing cycle
The motor is over-
heating
Check the flue gas temperature at the fan inlet. The temperature should not exceed 
500°F (300°C) during continuous operation. Call EXHAUSTO for advise.
  
6.3 Troubleshooting