    3.  Mechanical Installation
   
3.1  General
 
Warning: Failure to install, maintain and/or operate the RSIB Power Venter in accordance with 
the manufacturer’s instructions may result in conditions which can produce bodily injury and 
property damage.
The RSIB must be installed by a qualified installer in accordance with these instructions and all local codes, or
 
in their absence, with the latest edition of The National Fuel Gas Code (NFPA54/ANSI223.1), NFPA 211, NFPA 31  
 
or Canada CAN/CSA-B149.1-05 National Gas and Propane Installation Code when applicable. The RSIB must be  
 
mounted so the clearance to combustibles is at least 24 inches.
 
Preferably, the RSIB should be installed as close to the termination as possible. It can also be installed near the   
 
outlet of a heating appliance in the breeching itself, or in the transition from breeching to vertical chimney (replacing  
 
the Tee). In addition, it can be used for sidewall vented applications where it discharges through a wall.  The RSIB   
 
contains two drain holes to allow condensation to exit the fan housing.
 
The RSIB is for indoor and outdoor installation.  Unless installed adjacent to the wall it is discharging through,  
 
the chimney material used on the discharge side must be airtight/pressure rated. Traditional gas vent (B-vent) is not  
 
considered pressure rated or airtight.  The vent pipe must be installed and supported according to the chimney    
 
manufacturer’s instructions and/or in accordance with NFPA54, NFPA211 and Canada CAN/CSA-B149.1-05.  The  
RSIB collars fit most commonly available vents and stacks.
   
3.2  Positioning
 
The power venter can be installed in multiple positions. However, it should always be possible to remove the  
 
 
access door.
 
Acceptable power venter positions are shown below in Fig. 2.  Note that the power venter should never be installed  
 
so the motor points down.  This will cause condensation build up around the motor shaft and shorten the life of the  
 
motor.
 
RSIB350-500:  A drain hole located at the base of the motor MUST be removed prior to installation.  Failure to do so  
 
 
could shorten the life of the motor.  See Fig. 2 below.
Warning! Never install the power venter so the motor points down. This will shorten the life. The 
min. clearance to combustibles is 24 inches.
Fig. 2