Emerson 5500 SERIES Manuale Utente

Pagina di 43
monitor CMOS battery level. 
 
Symptom 
Possible 
Problem 
Possible 
Cause 
Action Prevention 
10. Email alarms were not sent 
out. 
 
No email 
was received 
by expecting 
recipients 
when alarm 
happens. 
 – No outgoing mail server 
address specified to the 
TWS. 
 – No originating email 
address specified to the 
TWS. 
 – Incorrect receiving email 
addresses specified to the 
TWS. 
 – Specify an outgoing mail server address 
given to you by the LAN administrator. 
 – Assign an originating email address to 
the TWS. This item is found in the 
Company info section of the TSSP. 
 – Make sure all the receiving email 
addresses are correct and valid. 
 – Make sure to coordinate and only 
use data disclosed to you by the 
LAN administrator. 
 – Review all information first in the 
TSSP before saving and uploading 
to the TWS. 
11. TWS reboots during 
runtime. 
 
Intermittent 
system 
failure. 
 – Data collisions in the 
network. 
 – Unknown Internal DB 
engine problem. 
 – Hard drive problem during 
file saving at runtime.  
 – Maximum system 
utilization reached, and no 
more resources are 
available to use. 
 – Internal thread problem. 
 – Hackers.  
 – System will always try to revive itself 
when there are unknown internal 
problems or restrictions not allowing it 
to continue its normal operation. This is 
to ensure that the TWS will always be 
available and running. 
 – Contact ASI for assistance if the TWS 
keeps resetting for no apparent reason 
and cannot resume to normal operation. 
 – Make sure to notify your LAN 
administrator if sympton persists. 
 – Give access only to known 
personnel. 
 – Make sure that the TWS has a 
unique IP address in the LAN. 
 – Check the content of the log 
directory to keep track of the 
history of the system from its last 
reboot. 
 – Keep in touch with ASCO Power 
Technologies for new releases and 
service packs. 
12. TSSP cannot connect to 
TWS. 
 
No 
connection 
between the 
computer 
and the 
TWS. 
 – Incorrect serial cable used. 
 – TSSP was not configured to 
the right port being used. 
 – Damaged comm. port. 
 – Damaged serial cable used. 
 
 – Check serial connection of the client 
station running the TSSP and the TWS. 
 – Make sure you are connected to COM1 
of the TWS. 
 – Check if you are using the right cable. 
You must use the serial cable that came 
with the product. 
 – Configure the TSSP properly, assigning 
only the appropriate port and baud rate 
settings. 
 – Use another available port. 
 – Use another spare serial cable. 
 
 – Follow this Installation Manual for 
how to install the TWS and use the 
TSSP.