CyberPower Network Management Card Manuale Utente

Pagina di 21
Cyber
Power Network Management System 
 
Description 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1) Serial Port
 provides a connection for communication between the UPS and the Network 
Management Card 
2) Reset Button is used to reset the settings. When the Reset Button is pushed for 3 seconds, 
all settings except for the IP address for Network Management Card will refresh to default 
values.    When the Reset Button is pushed for more than 3 seconds, all settings including the 
IP address for CyberPower Network Management Card will reset to default values. 
3) DC power input allows input of power from the AC adapter(for select UPS models only) into 
wall socket. The DC power input is only used when the Network Management card is 
connected to select UPS models that don’t supply power to the Network Management Card. 
4) MSG Indicator indicates the status of connection between UPS and the Network 
Management Card. This indicator light will flash when Network Management Card IS NOT 
connected to the UPS. 
5) PWR Indicator indicates the power is on or off.    It illuminates when the Network 
Management Card is powered ON. 
6) LINK Indicator indicates the status of network connection. It illuminates when the Network 
Management Card is connected to the network. 
7) 10M Ethernet connector 
 
Definitions for LED Indicators 
Indicator Mode 
Condition 
Off 
The Network Management Card is connected to UPS 
MSG  
(Red) 
Flashing 
No connection between the Network Management Card and 
the UPS 
Off 
The Network Management Card Power Is Off 
PWR 
(Green) 
On 
The Network Management Card Power Is On 
Off 
The Network Management Card is disconnected to the 
Network 
LINK 
(Yellow) 
On 
The Network Management Card is connected to the Network