Fujitsu DX60S2 Manuale Utente

Pagina di 62
Chapter 2  ETERNUS DX Disk Storage System Installation
  2.6  Circuit Protectors
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
37
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
2.6.2
Breaking Characteristics
For power distribution unit (2U) connection
The breaking characteristics (*1) of distribution board circuit protectors must be slower than the 
values shown in 
 or equivalent to D (IEC898).
*1:
Relationship between the size of excess current and operation time
Figure 2.4
Power distribution unit (2U) breaking characteristics (graph)
Table 2.10 Power distribution unit (2U) breaking characteristics (Trip time (sec.))
Delay
100%
125%
150%
200%
400%
600%
800%
1000%
63
No Trip
50 to 
700
30 to 
400
10 to 
150
1.5 to 
20
0.4 to 
10
0.013 to 
0.85
0.013 to 
0.5
150
100
200
300
400
500
600
700
800
900
1000
0
125
PERCENT OF RATED CURRENT
100
1000
10000
10
1
.1
.01
.001
TIME IN SECONDS
DELAY 63
MA
Y TRIP