Cooper Lighting 84700 Manuale Utente

Pagina di 41
9131 
Rev. M 
 
TABLE 4-2 
 
TROUBLESHOOTING PROCEDURE 
 
 
PROBLEM 
POSSIBLE CAUSE 
TEST 
CORRECTIVE ACTION 
CSC does not 
operate in remote 
(all circuits) 
Power source not 
energized 
Verify voltage is 
present at TB1-L, LN 
Restore power 
 
Blown fuse 
Check F1 
Replace fuse 
 
 
Broken wire 
Check wiring harness 
Repair or replace harness 
assy 
 
One or two circuits 
of CSC do not 
operate in local or 
remote 
Broken wire 
Check wiring harness 
Repair or replace harness 
assy 
 
Loose or defective 
H.V. relay module 
Check connector 
Re-seat connector on 
Timing Circuit Card 
 
 
 
Check relay control 
harness 
Repair or replace relay 
harness 
 
Regulator trips off 
when one or more 
circuits are 
activated 
Miswired lighting 
----- 
Check all wiring 
 
Defective relay or 
open lighting circuit 
Disconnect wires to 
R1 & R2 using an 
ohmmeter, determine 
fault location 
 
Repair lighting circuit or 
replace relay module or 
faulty relay 
Regulator current 
falls when light 
circuit is activated 
 
regulator capacity is 
insufficient 
Calculate total load 
requirements 
Use a larger regulator 
CSC does not 
operate in remote 
Remote control wires 
connected incorrectly 
or broken 
 
Check remote 
connections 
Repair remote control 
equipment 
 
Defective timing 
circuit 
------ 
If remote control signals are 
correct, the problem is 
probably due to a defective 
timing circuit card.  
Observe all precautions of 
para. 4.2 when replacing 
the timing circuit card 
 
 
 
 
 
 
 
 
18