5.3.2 Server Specific Map Descriptor Parameters – Unconnected Messages
Column Title
Function
Legal Values
EIP_Service
The action to be performed.
Get_Attrib, Set_Attrib
EIP_Class
Class to be served.
One
of
the
classes
supported by the driver. .
Refer to Appendix A.4
Refer to Appendix A.4
EIP_Attribute Attribute associated with the class served.
Length
Number of data elements to be mapped. If the number of data
elements exceeds the Map Descriptor length, the list of data
elements will be truncated and an error message will be printed
once per Map Descriptor. Refer to Appendix C for further
information.
elements exceeds the Map Descriptor length, the list of data
elements will be truncated and an error message will be printed
once per Map Descriptor. Refer to Appendix C for further
information.
For
any
given
Map
Descriptor there can be
200 Floats, 400 Integers or
800 Bytes
200 Floats, 400 Integers or
800 Bytes
Address
Instance of the class to be served.
Depends
on
the
supported instances for
each class.
each class.
5.3.3 Server Specific Map Descriptor Parameters – Data Table Read/Write.
Column Title
Function
Legal Values
EIP_Service
The action to be performed.
Data_Table_Read,
Data_Table_Write
Data_Table_Write
EIP_Tag_Name
Tag name expressed in PLC program. The data type of this
parameter is used to set the data format of the Data Array
if the EIP_Data_Type parameter is not specified.
parameter is used to set the data format of the Data Array
if the EIP_Data_Type parameter is not specified.
Maximum
length
48
characters.
EIP_Data_Type*
If set, the data will be stored in the specified format which
may be different to the format of the tag being polled. If
the parameter is not set, the data type of the Data Array
will be used. This is only applicable to Data Table Read
when FieldServer is the Server. Refer to Appendix A.4 for
further information.
may be different to the format of the tag being polled. If
the parameter is not set, the data type of the Data Array
will be used. This is only applicable to Data Table Read
when FieldServer is the Server. Refer to Appendix A.4 for
further information.
Float, Uint16, Uint32, Bit,
Byte, Boolean, -
Byte, Boolean, -
Length
Number of data elements to be mapped. If the number of
data elements exceeds the Map Descriptor length, the list
of data elements will be truncated and an error message
will be printed once per Map Descriptor. Refer to
Appendix C for further information.
data elements exceeds the Map Descriptor length, the list
of data elements will be truncated and an error message
will be printed once per Map Descriptor. Refer to
Appendix C for further information.
For
any
given
Map
Descriptor there can be
200 Floats, 400 Integers
or 800 Bytes
200 Floats, 400 Integers
or 800 Bytes
EIP_Structure_Handle*
This parameter is required only for read structures i.e.
where EIP_Service is Data_Table_Read. The driver
supports read structures having members of same type,
i.e. all members are of type Byte, Uint16, Uint32 or Float
etc. When this parameter is defined, the number of
structure members must be specified as the length of the
Map Descriptor.
where EIP_Service is Data_Table_Read. The driver
supports read structures having members of same type,
i.e. all members are of type Byte, Uint16, Uint32 or Float
etc. When this parameter is defined, the number of
structure members must be specified as the length of the
Map Descriptor.
Any 16bit Integer number
e.g. 59592, 0
e.g. 59592, 0