FS-8704-14 EtherNet/IP Manual 
 
 
 
 
 
 
 
Page 20 of 30 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
Step 4 
Configure the Properties for the two Message Blocks by clicking on the “…” button: 
Read Message Block: 
  
Write Message Block: 
 
 
Communication Tab for both Message Blocks: 
 
Step 5 
Download the program and set the PLC to Run Mode. 
Remote FieldServer Tag Configured in the FieldServer (see example above) 
Local PLC Tag configured in the PLC Tag List (see example above) 
Local PLC Tag configured in the PLC Tag List (see example above) 
Remote FieldServer Tag configured in the FieldServer (see example above) 
Number of points transferred from FieldServer 
to PLC regardless of Tag and Array Sizes 
Number of points transferred from PLC to FieldServer 
regardless of Tag and Array Sizes 
EIP_Card is the name of the Ethernet ENBT Card in the 
ControlLogix Rack. 
“2” refers to the port number on the ENBT Card. 
192.168.1.75 is the IP Address of the FieldServer. 
The Tag Tab requires no configuration.