Identifying Parameter Defaults For Carrier Drives
4-1
C
HAPTER
4
Identifying Parameter Defaults
For Carrier Drives
Use the following table to identify and set the parameter defaults for Carrier drives.
Important:
Setting P.050 (Restore Defaults) to ON will restore the drive to Reliance defaults,
not Carrier defaults. If this has been done, set the following parameters to restore
Carrier defaults
not Carrier defaults. If this has been done, set the following parameters to restore
Carrier defaults
.
For job-specific parameters, refer to the 19XR, XRV Start-Up, Operation, and Maintenance
Instructions manual (531-982) for further instructions. For descriptions of all parameters, refer to
the LiquiFlo Software Start-Up and Reference manual (D2-3410).
Instructions manual (531-982) for further instructions. For descriptions of all parameters, refer to
the LiquiFlo Software Start-Up and Reference manual (D2-3410).
Parameter No.
Parameter Name
Setting
P.000 Control
Source
rE
P.001
Accel Time 1
8
P.002
Decel Time 1
20
P.003
Minimum Speed
0.5
P.004
Maximum Speed
Job-specific (50 or 60)
P.005
Current Limit
110
P.009
1
1
These parameters must be tuned or calibrated per the VFD Control Verification procedures (running and
non-running) found in the Carrier 19XR/XRV Start-Up, Operation, and Maintenance Instructions on pages
59-60.
59-60.
Terminal Strip Analog Input Offset
-10
P.010
Terminal Strip Analog Input Gain
0.99 (50LR4060, 64LR4060)
1.030 (41LR4060)
P.011
Terminal Strip Analog Input Configure
4
P.013
Output Relay Configuration
2
P.027
Forward/Reverse Configuration
1
P.028
Speed Display Scaling
Job-specific
P.043
Fault Auto Reset Attempts
10
P.044
Fault Auto Reset Time
30
P.052
AUTO/MAN Key Disable
ON
H.000
Motor Nameplate Volts
Job-specific
H.001
Motor Nameplate Base Frequency
Job-specific
H.002
Motor Nameplate Amps
1.03 x Motor Nameplate Amps
H.021
AC Line Volts
Job-specific
H.022
Overfrequency Limit
Job-specific (57 or 69)
r.001
Analog Output 1 Source
4
r.002
Analog Output 1 Offset
60 (50LR4060, 64LR4060)
135 (41LR4060)
r.003
Analog Output 1 Gain
0.505 (50LR4060, 64LR4060)
0.503 (41LR4060)
r.035
Relay Output 1 (NO) Configuration
5
r.036
Relay Output 2 (NO/NC) Configuration
2
r.037
Relay Output 3 (NO/NC) Configuration
1
r.046
Relay Output 3 Delay Time
-999
r.050
Speed Detection Level 1
35