6-8
Carrier VFD Quick Reference
6.4.2 Identifying Fault Codes and Recovering
Drive fault codes are shown in table 6.3. To clear a single fault that has occurred so 
that the drive can be started again, correct any problems indicated by the fault code 
and press the STOP/RESET key on the keypad, or assert the fault reset from the 
selected control source (P.000). Because multiple faults can occur and only the first 
will be displayed, you must access the error log in order to view all of the faults that 
have occurred. See section 6.4.3 for instructions on how to view the error log.
!
ATTENTION: DC bus capacitors retain hazardous voltages after input 
power has been disconnected. After disconnecting input power, wait five 
minutes for the DC bus capacitors to discharge and then check the 
voltage with a voltmeter to ensure the DC bus capacitors are discharged 
before touching any internal components. Failure to observe this 
precaution could result in severe bodily injury or loss of life.
Table 6.3 – List of Fault Codes
Code
Fault
Description
Fault Cause
Corrective Action
AIn
Analog input signal 
loss
P.011 = 4 or 5 and 4 to 20 mA analog 
input is below 1 mA.
Verify that P.011 is set correctly.
Check that the analog input source 
supply 
≥1 mA.
bYC
Incorrect precharge 
status
Precharge initiated and incorrect 
precharge status is returned.
Check operation of the precharge. 
CHS
Default parameter 
restore (checksum 
error)
During drive operation:
Regulator board failure.
Contact Reliance or replace Regulator 
board.
After Regulator board replacement:
Contact Reliance.
EC
Earth current failure 
(ground fault)
Unintentional grounding of the input.
Check isolation between ground and 
output terminals. Possible leakage, 
current sensor defects; replace 
sensor.
EEr
Non-volatile 
memory write
failure
Failure on write to non-volatile 
memory.
Connect CS3000 software to upload 
parameters or record by hand. Then 
replace Regulator board. Parameter 
values will be lost when power is 
cycled.
EL
Encoder loss
Drive is not detecting feedback from 
the encoder.
For SVC operation, conditions exist for 
more than 5 seconds that may result in 
an inability to complete a ramp-to-rest 
stop.
Check the connection between the 
encoder and the drive. Check the 
encoder/motor coupling.
For SVC operation, check motor data 
parameters. Check U.006. Incorrect 
magnetizing current may be generated 
by performing self-tuning with a load 
connected to the motor.
FL
Function loss
Function loss input on control terminal 
is opened.
Check external interlocks at terminals 
16, 20.
HId
High time 
identification 
aborted
Identification process for V/Hz has 
been aborted.
See H.019 for identification result.
HIL
High line voltage
Input voltage more than 15% above 
nominal. 
Check actual line voltage against 
U.018 or H.021.